| Specification |
Details |
| Model |
9905-969 |
| Series |
LinkNet |
| Type |
Analog Input Module |
| Number of Channels |
6 |
| Input Signal |
4–20 mA |
| Loop Power |
24 VDC |
| Power Supply Input |
18–32 VDC, 1 A at 24 VDC |
| Accuracy |
1% at 25°C |
| Isolation |
Network to I/O channel: 277 VAC; Power supply input to network: 277 VAC; Power supply input to I/O channel: 500 V |
| Update Time |
5 ms (estimated, based on LinkNet standards) |
| Display |
2-line x 24-character LCD |
| Keypad |
30 multi-function keypad |
| Operating Temperature |
-40°C to +55°C (-40°F to +131°F) |
| Storage Temperature |
-40°C to +85°C (-40°F to +185°F) |
| Relative Humidity |
95% non-condensing at 20–55°C for 48 hours |
| Vibration |
4 G, 5–500 Hz |
| Shock |
20 G peak |
| Protection Rating |
IP20 (designed for control cabinet use) |
| Dimensions |
355 mm x 279 mm x 102 mm (14 in x 11 in x 4 in) |
| Weight |
Approximately 4.13 kg (9.11 lbs) |
| Mounting |
DIN-rail or panel mount in Phoenix field termination module package |
| Certifications |
CE, UL/cUL (estimated for industrial environments) |
| System Compatibility |
Woodward NetCon, MicroNet, turbine/engine control systems |