Product Description
Woodward 8406-121 EGCP-2 Engine Generator Control Package
- Manufacturer: Woodward
- Model/Part Number: 8406-121, Revision H
- Description: EGCP-2 Microprocessor-Based Generator Control and Engine Management Package, 50_150 VAC PT Input, 9_32 VDC, for Diesel or Gas Engine Generator Sets
Overview
- The Woodward 8406-121 (Rev. H) is an EGCP-2 Engine Generator Control Package designed for automating and protecting small- to medium-sized diesel or gas engine-based generator sets (up to 30,000 kW). It integrates with an automatic voltage regulator and speed control for comprehensive generator management, supporting stand-alone or utility-paralleled operations. A network of up to eight EGCP-2 units can control unmanned generator sets for base-load, peak shaving, or backup power applications.
Technical Specifications
| Specification | Details |
|---|---|
| Model | 8406-121, Revision H |
| Series | EGCP-2 |
| Type | Microprocessor-Based Generator Control |
| Power Supply | 9_32 VDC (SELV), 13 W nominal, 20 W maximum |
| Input Supply Current | 1.08 A (12 V), 542 mA (24 V), 406 mA (32 V) |
| Potential Transformer (PT) Inputs | 4 inputs, 50_150 VAC, 0.25 VA burden, 40_70 Hz |
| Current Transformer (CT) Inputs | 0_5 A RMS, 40_70 Hz |
| Analog Input | 1 input, 0_5 VDC or 4_20 mA DC |
| Discrete Inputs | 16 inputs, 5 mA each when closed to switch common (terminal 65), 80 mA total max |
| Temperature/Pressure Inputs | 0_200 Ω sensors, 4_20 mA or 0_5 V transducers |
| Magnetic Pickup (MPU) | 100_10,000 Hz |
| Speed Bias Output | ±3 VDC, 0.5_4.5 VDC, or 5 V peak 500 Hz PWM |
| Voltage Bias Output | ±1 VDC, ±3 VDC, or ±9 VDC |
| Discrete Outputs (Relay) | 10 A, 250 VAC resistive; 249 W (1/3 hp), 125 VAC (7.2 A, 0.4_0.5 PF); 10 A, 30 VDC resistive |
| Communication Ports | RS-485, RS-422, Modbus RTU |
| Display | Two backlit LCD screens (8 lines status, 4 lines config/alarm log) |
| Operating Temperature | -20°C to +70°C (-4°F to +158°F) |
| Storage Temperature | -40°C to +105°C (-40°F to +221°F) |
| Relative Humidity | 95% non-condensing at 20_55°C |
| Vibration | SV2 5_2000 Hz @ 4 G, RV1 10_2000 Hz @ 0.04 G²/Hz |
| Shock | US MIL-STD 810C, Method 516.2, Procedures I, II, V |
| Ingress Protection | IP56 (when in vented enclosure) |
| Dimensions | 282 x 358 x 69 mm (11.1 x 14.1 x 2.7 in) |
| Weight | Approximately 2.97 kg (6.55 lbs) |
| Mounting | Panel mount, M5 x 12 mm thread-forming screws |
| Certifications | CE, UL/cUL (non-hazardous locations only) |
| System Compatibility | Woodward speed controls, AVRs, diesel/gas engines |
_