| Specification |
Details |
| Model |
8406-121, Revision H |
| Series |
EGCP-2 |
| Type |
Microprocessor-Based Generator Control |
| Power Supply |
9–32 VDC (SELV), 13 W nominal, 20 W maximum |
| Input Supply Current |
1.08 A (12 V), 542 mA (24 V), 406 mA (32 V) |
| Potential Transformer (PT) Inputs |
4 inputs, 50–150 VAC, 0.25 VA burden, 40–70 Hz |
| Current Transformer (CT) Inputs |
0–5 A RMS, 40–70 Hz |
| Analog Input |
1 input, 0–5 VDC or 4–20 mA DC |
| Discrete Inputs |
16 inputs, 5 mA each when closed to switch common (terminal 65), 80 mA total max |
| Temperature/Pressure Inputs |
0–200 Ω sensors, 4–20 mA or 0–5 V transducers |
| Magnetic Pickup (MPU) |
100–10,000 Hz |
| Speed Bias Output |
±3 VDC, 0.5–4.5 VDC, or 5 V peak 500 Hz PWM |
| Voltage Bias Output |
±1 VDC, ±3 VDC, or ±9 VDC |
| Discrete Outputs (Relay) |
10 A, 250 VAC resistive; 249 W (1/3 hp), 125 VAC (7.2 A, 0.4–0.5 PF); 10 A, 30 VDC resistive |
| Communication Ports |
RS-485, RS-422, Modbus RTU |
| Display |
Two backlit LCD screens (8 lines status, 4 lines config/alarm log) |
| Operating Temperature |
-20°C to +70°C (-4°F to +158°F) |
| Storage Temperature |
-40°C to +105°C (-40°F to +221°F) |
| Relative Humidity |
95% non-condensing at 20–55°C |
| Vibration |
SV2 5–2000 Hz @ 4 G, RV1 10–2000 Hz @ 0.04 G²/Hz |
| Shock |
US MIL-STD 810C, Method 516.2, Procedures I, II, V |
| Ingress Protection |
IP56 (when in vented enclosure) |
| Dimensions |
282 x 358 x 69 mm (11.1 x 14.1 x 2.7 in) |
| Weight |
Approximately 2.97 kg (6.55 lbs) |
| Mounting |
Panel mount, M5 x 12 mm thread-forming screws |
| Certifications |
CE, UL/cUL (non-hazardous locations only) |
| System Compatibility |
Woodward speed controls, AVRs, diesel/gas engines |