Woodward 8406-121 EGCP-2 Engine Generator Control Package
- Manufacturer: Woodward
- Model/Part Number: 8406-121, Revision H
- Description: EGCP-2 Microprocessor-Based Generator Control and Engine Management Package, 50–150 VAC PT Input, 9–32 VDC, for Diesel or Gas Engine Generator Sets
Overview
- The Woodward 8406-121 (Rev. H) is an EGCP-2 Engine Generator Control Package designed for automating and protecting small- to medium-sized diesel or gas engine-based generator sets (up to 30,000 kW). It integrates with an automatic voltage regulator and speed control for comprehensive generator management, supporting stand-alone or utility-paralleled operations. A network of up to eight EGCP-2 units can control unmanned generator sets for base-load, peak shaving, or backup power applications.
Technical Specifications
Specification | Details |
---|---|
Model | 8406-121, Revision H |
Series | EGCP-2 |
Type | Microprocessor-Based Generator Control |
Power Supply | 9–32 VDC (SELV), 13 W nominal, 20 W maximum |
Input Supply Current | 1.08 A (12 V), 542 mA (24 V), 406 mA (32 V) |
Potential Transformer (PT) Inputs | 4 inputs, 50–150 VAC, 0.25 VA burden, 40–70 Hz |
Current Transformer (CT) Inputs | 0–5 A RMS, 40–70 Hz |
Analog Input | 1 input, 0–5 VDC or 4–20 mA DC |
Discrete Inputs | 16 inputs, 5 mA each when closed to switch common (terminal 65), 80 mA total max |
Temperature/Pressure Inputs | 0–200 Ω sensors, 4–20 mA or 0–5 V transducers |
Magnetic Pickup (MPU) | 100–10,000 Hz |
Speed Bias Output | ±3 VDC, 0.5–4.5 VDC, or 5 V peak 500 Hz PWM |
Voltage Bias Output | ±1 VDC, ±3 VDC, or ±9 VDC |
Discrete Outputs (Relay) | 10 A, 250 VAC resistive; 249 W (1/3 hp), 125 VAC (7.2 A, 0.4–0.5 PF); 10 A, 30 VDC resistive |
Communication Ports | RS-485, RS-422, Modbus RTU |
Display | Two backlit LCD screens (8 lines status, 4 lines config/alarm log) |
Operating Temperature | -20°C to +70°C (-4°F to +158°F) |
Storage Temperature | -40°C to +105°C (-40°F to +221°F) |
Relative Humidity | 95% non-condensing at 20–55°C |
Vibration | SV2 5–2000 Hz @ 4 G, RV1 10–2000 Hz @ 0.04 G²/Hz |
Shock | US MIL-STD 810C, Method 516.2, Procedures I, II, V |
Ingress Protection | IP56 (when in vented enclosure) |
Dimensions | 282 x 358 x 69 mm (11.1 x 14.1 x 2.7 in) |
Weight | Approximately 2.97 kg (6.55 lbs) |
Mounting | Panel mount, M5 x 12 mm thread-forming screws |
Certifications | CE, UL/cUL (non-hazardous locations only) |
System Compatibility | Woodward speed controls, AVRs, diesel/gas engines |