| Module Type |
Triple Modular Redundant (TMR), Single-Ended Analog Input, Non-Isolated |
| Input Points |
32 single-ended inputs |
| Input Types |
0-5 V DC, 0-10 V DC, 4-20 mA (with external 250 Ω resistor) |
| Resolution |
12 bits |
| Accuracy |
±0.15% of full scale at 25°C |
| Input Impedance |
>1 MΩ for voltage inputs, 250 Ω for current inputs (with external resistor) |
| Common Mode Rejection Ratio |
>80 dB at 60 Hz |
| Update Rate |
50 ms for all channels |
| Power Supply |
24 V DC nominal (18-36 V DC range) via Trident chassis |
| Power Consumption |
5 W typical |
| Diagnostics |
Built-in diagnostics for open circuit, over-range, and under-range conditions |
| Operating Temperature |
0°C to 60°C (32°F to 140°F) |
| Storage Temperature |
-40°C to 85°C (-40°F to 185°F) |
| Humidity |
5% to 95% (non-condensing) |
| Mounting |
Plugs into Trident Analog Input Baseplate |
| Standards Compliance |
SIL 3 (IEC 61508), CE, UL, CSA, ATEX (for hazardous locations) |