Channels |
32 analog input channels, single-ended |
Input Types |
4-20 mA, 0-5 V DC, 0-10 V DC |
Resolution |
12 bits |
Accuracy |
±0.15% of full scale at 25°C |
Input Impedance |
>1 MΩ for voltage inputs, 250 Ω for current inputs (with external resistor) |
Isolation |
Channel-to-channel and channel-to-system isolation, 1500 V AC |
Update Rate |
50 ms for all channels |
Power Supply |
24 V DC nominal (18-36 V DC range) via Trident baseplate |
Power Consumption |
5 W typical |
Diagnostics |
Built-in diagnostics for open circuit, over-range, and under-range conditions |
Operating Temperature |
0°C to 60°C (32°F to 140°F) |
Storage Temperature |
-40°C to 85°C (-40°F to 185°F) |
Humidity |
5% to 95% (non-condensing) |
Mounting |
Plugs into Trident Analog Input Baseplate |
Standards Compliance |
SIL 3 (IEC 61508), CE, UL, CSA, ATEX (for hazardous locations) |