Product Description
General Information
Field |
Details |
---|---|
Manufacturer |
Schneider Electric |
Model/Part Number |
ATV312HD11N4 |
Description |
Variable speed drive ATV312 - 11kW - 25kVA - 397 W - 380..500 V - 3-phase supply |
Range of Product |
Altivar 312 |
Product Type |
Variable speed drive |
Application |
For asynchronous motors – simple machines |
Assembly Style |
With heat sink |
Component Name |
ATV312 |
Technical Specifications
Electrical Specifications
Parameter |
Value |
---|---|
Rated Supply Voltage [Us] |
380…500 V (-15% to +10%) |
Supply Frequency |
50…60 Hz ±5% |
Supply Voltage Limits |
323…550 V |
Line Current |
37.2 A @ 380 V; 28.4 A @ 500 V |
Maximum Transient Current |
41.6 A for 60 seconds |
Apparent Power |
25 kVA |
Continuous Output Current |
27.7 A @ 4 kHz |
Output Frequency |
0…500 Hz |
Switching Frequency |
2…16 kHz adjustable (nominal 4 kHz) |
Power Dissipation |
397 W at nominal load |
Speed Range |
1…50 |
Motor Control |
Sensorless flux vector control (PWM), constant torque |
Transient Overtorque |
170–200% of nominal torque |
Braking Torque |
Up to 150% (with or without resistor) |
Regulation Loop |
Frequency PI regulator |
Output Voltage |
≤ Supply voltage |
I/O & Communication
Type |
Details |
---|---|
Analog Inputs |
3 (AI1: 0–10V, AI2: ±10V, AI3: 0–20mA) |
Analog Outputs |
1 (AOC: 0–20mA, AOV: 0–10V) |
Discrete Inputs |
6 (24V, 0–100 mA, 3500 Ω impedance) |
Discrete Outputs |
2 configurable relays (R1A/B/C, R2A/B) |
Minimum Switching Current |
10 mA @ 5 V DC |
Max Switching Current |
Up to 5 A @ 250 V AC / 30 V DC |
Sampling Time |
Analog: 8 ms, Discrete: 4 ms |
Communication Ports |
RS485 with RJ45 (Modbus/CANopen) |
Protocols |
Modbus, CANopen |
Supported Baud Rates |
CANopen: up to 1 Mbps; Modbus: up to 19200 bps |
Device Address Range |
CANopen: 1–127; Modbus: 1–247 |
Max No. of Drives |
127 (CANopen), 31 (Modbus) |
Protection & Safety
Feature |
Details |
---|---|
Protection Types |
Input/motor phase loss, short circuit, overcurrent, overvoltage, overheating, DC injection braking |
Insulation Resistance |
≥ 500 MΩ @ 500 V DC for 1 minute |
Dielectric Strength |
2410 V DC (earth to power); 3400 V AC (control to power) |
Standards |
IEC 61800-5-1, IEC 61800-3 |
Certifications |
CE, UL, CSA, NOM, C-Tick, GOST, DNV |
Environmental Specifications
Parameter |
Value |
---|---|
IP Protection |
IP20 (top), IP21/IP31/IP41 (terminal/top, depending on cover) |
Shock Resistance |
15 gn for 11 ms (IEC 60068-2-27) |
Vibration Resistance |
1 gn (13–150 Hz), 1.5 mm (3–13 Hz) |
Humidity |
5–95% non-condensing/non-dripping (IEC 60068-2-3) |
Ambient Temperature |
Operation: -10…50°C (w/ cover), -10…60°C (w/ derating) |
Storage Temperature |
-25…70°C |
Altitude |
≤1000 m (no derating), up to 3000 m (1% derating per 100 m) |
Pollution Degree |
2 |
Protective Treatment |
TC |
Physical Specifications
Parameter |
Value |
---|---|
Dimensions |
329.5 x 245 x 192 mm |
Net Weight |
11 kg |
Tightening Torque |
0.6 N·m (control), 4.5 N·m (power) |
Packaging Information
Package Type |
Quantity |
Dimensions (L x W x H) (cm) |
Weight |
---|---|---|---|
PCE (Unit 1) |
1 |
38.5 x 30.0 x 28.0 |
11.755 kg |
P06 (Unit 2) |
4 |
60.0 x 80.0 x 80.0 |
Not specified |