Product Description
General Information
|
Field |
Details |
|---|---|
|
Manufacturer |
Schneider Electric |
|
Model/Part Number |
ABL8RPS24100 |
|
Description |
Regulated switch mode power supply, Modicon series, 1/2-phase, 24__DC, 10__ |
_
_
Specifications
_
Main
|
Parameter |
Value |
|---|---|
|
Range of Product |
Modicon Power Supply |
|
Product Type |
Power supply |
|
Power Supply Type |
Regulated switch mode |
|
Nominal Input Voltage |
100_120__ AC (single phase), 200_500__ AC (phase-to-phase) |
|
Rated Output Power |
240__ |
|
Output Voltage |
24__ DC |
|
Output Current |
10__ |
|
Temporary Current Boost |
1.5 _ In for 4__ |
|
Anti-Harmonic Filter |
Low frequency harmonic currents |
_
Complementary
|
Parameter |
Value |
|---|---|
|
Input Voltage Limits |
85_132__ AC / 170_550__ AC |
|
Inrush Current |
30__ |
|
Power Factor |
0.69 at 120__ AC, 0.68 at 240__ AC |
|
Efficiency |
87% |
|
Output Voltage Adjustment |
24_28.8__ adjustable |
|
Power Dissipation |
31__ |
|
Provided Equipment |
Power factor correction filter (IEC 61000-3-2) |
|
Output Protections |
Overload, Overvoltage (30_32__), Short-circuit, Undervoltage (<21.6__), Thermal |
|
Connection Terminals |
Screw terminals, removable terminal block for diagnostic relay |
|
Status LEDs |
Output voltage (Green/Red), Output current (Green/Red/Orange) |
|
Dimensions (W x H x D) |
86 _ 125 _ 145 mm |
|
Net Weight |
1__g |
|
Output Coupling |
Parallel, Series |
|
Mounting Support |
35__m DIN rail (7.5/15__m) |
|
Operating Position |
Vertical |
|
SELV Compliance |
IEC 60950-1, IEC 60204-1, IEC 60364-4-41 |
|
Dielectric Strength |
3500__ (input-ground), 4000__ (input-output), 500__ (output-ground) |
_
_
Environmental Characteristics
|
Parameter |
Value |
|---|---|
|
Standards |
UL 508, CSA C22.2 No 60950-1, EN/IEC 62368-1 |
|
Certifications |
CCSAus, EAC, KC, RCM, UL |
|
EMC Standards |
IEC 61000-6-1/6-3/6-4, EN 55024, EN/IEC 61204-3 |
|
Safety Standards |
IEC 60950-1, EN/IEC 61204-3 |
|
Operating Altitude |
Up to 2000__ |
|
IP Protection |
IP20 (IEC 60529) |
|
Ambient Temperature (Operation) |
-25 to 50__ (without derating) |
|
50 to 60__ (with derating) |
_