Product Description
General Information
|
Field |
Details |
|---|---|
|
Manufacturer |
Schneider Electric |
|
Model/Part Number |
ABL8RPS24100 |
|
Description |
Regulated switch mode power supply, Modicon series, 1/2-phase, 24 VDC, 10 A |
Specifications
Main
|
Parameter |
Value |
|---|---|
|
Range of Product |
Modicon Power Supply |
|
Product Type |
Power supply |
|
Power Supply Type |
Regulated switch mode |
|
Nominal Input Voltage |
100–120 V AC (single phase), 200–500 V AC (phase-to-phase) |
|
Rated Output Power |
240 W |
|
Output Voltage |
24 V DC |
|
Output Current |
10 A |
|
Temporary Current Boost |
1.5 × In for 4 s |
|
Anti-Harmonic Filter |
Low frequency harmonic currents |
Complementary
|
Parameter |
Value |
|---|---|
|
Input Voltage Limits |
85–132 V AC / 170–550 V AC |
|
Inrush Current |
30 A |
|
Power Factor |
0.69 at 120 V AC, 0.68 at 240 V AC |
|
Efficiency |
87% |
|
Output Voltage Adjustment |
24–28.8 V adjustable |
|
Power Dissipation |
31 W |
|
Provided Equipment |
Power factor correction filter (IEC 61000-3-2) |
|
Output Protections |
Overload, Overvoltage (30–32 V), Short-circuit, Undervoltage (<21.6 V), Thermal |
|
Connection Terminals |
Screw terminals, removable terminal block for diagnostic relay |
|
Status LEDs |
Output voltage (Green/Red), Output current (Green/Red/Orange) |
|
Dimensions (W x H x D) |
86 × 125 × 145 mm |
|
Net Weight |
1 kg |
|
Output Coupling |
Parallel, Series |
|
Mounting Support |
35 mm DIN rail (7.5/15 mm) |
|
Operating Position |
Vertical |
|
SELV Compliance |
IEC 60950-1, IEC 60204-1, IEC 60364-4-41 |
|
Dielectric Strength |
3500 V (input-ground), 4000 V (input-output), 500 V (output-ground) |
Environmental Characteristics
|
Parameter |
Value |
|---|---|
|
Standards |
UL 508, CSA C22.2 No 60950-1, EN/IEC 62368-1 |
|
Certifications |
CCSAus, EAC, KC, RCM, UL |
|
EMC Standards |
IEC 61000-6-1/6-3/6-4, EN 55024, EN/IEC 61204-3 |
|
Safety Standards |
IEC 60950-1, EN/IEC 61204-3 |
|
Operating Altitude |
Up to 2000 m |
|
IP Protection |
IP20 (IEC 60529) |
|
Ambient Temperature (Operation) |
-25 to 50 °C (without derating) |
|
50 to 60 °C (with derating) |