| Protection Functions |
Distance protection (21), directional overcurrent (67), non-directional overcurrent (50/51), earth fault (50N/51N/67N), pole slip (78), power swing detection (68), high-impedance fault detection |
| Measurement Capabilities |
Voltage, current, power, frequency, power factor; supports three-phase and residual measurements with disturbance recording |
| Binary Inputs/Outputs |
16 binary inputs, 10 output contacts (configurable) |
| Communication Interfaces |
2x Ethernet ports (IEC 61850, DNP3, Modbus TCP), 2x serial ports (SPA, IEC 60870-5-103) |
| Power Supply |
24-60 V DC or 48-265 V DC / 100-240 V AC options |
| Operating Temperature Range |
-25°C to +55°C |
| Dimensions |
177 mm x 177 mm x 144 mm (4U 19" rack mount) |
| Mounting |
19" rack or panel mount |
| Protection Rating |
IP54 front panel |
| Standards Compliance |
IEC 60255, ANSI/IEEE C37.2, CE, UL, CSA |