| Protection Functions |
Numerical differential protection (87), overcurrent (50/51), restricted earth fault (87N), 100% stator ground fault (64G), loss of excitation (40), over/under voltage (27/59), over/under frequency (81O/U) |
| Measurement Capabilities |
Voltage, current, power, frequency, rotor angle; supports up to 6 three-phase current inputs and 3 three-phase voltage inputs |
| Binary Inputs/Outputs |
18 binary inputs, 11 output contacts (configurable) |
| Communication Interfaces |
2x Ethernet ports (IEC 61850, DNP3, Modbus TCP), 2x serial ports (SPA, IEC 60870-5-103) |
| Power Supply |
24-60 V DC or 48-250 V DC / 100-240 V AC options |
| Operating Temperature Range |
-25°C to +55°C |
| Dimensions |
177 mm x 177 mm x 144 mm (4U 19" rack mount) |
| Mounting |
19" rack or panel mount |
| Protection Rating |
IP54 front panel |
| Standards Compliance |
IEC 60255, IEEE C37.102, CE, UL, CSA |