Product Description
Product Details
Manufacturer |
JUMO |
---|---|
Model/Part Number |
701160/8-0153-001-23 |
Description |
Temperature Limiter, Temperature Monitor |
Technical Specifications
1. Analog Inputs
Resistance Thermometers
Designation |
Measuring Range |
Accuracy |
Connection Circuit |
Sampling Rate |
Input Filter |
Features |
---|---|---|---|---|---|---|
Pt100 EN 60751 |
-200°C to +850°C |
0.1% |
2-wire, 3-wire |
210 ms |
2nd order digital filter; adjustable from 0 to 100 sec |
2 x Pt100 for differential measurement; display can be programmed in °F |
KTY11-6 PTC |
-50°C to +150°C |
1% |
2-wire, 3-wire |
210 ms |
2nd order digital filter; adjustable from 0 to 100 sec |
Display can be programmed in °F |
Pt1000 EN 60751 |
-200°C to +850°C |
0.1% |
2-wire, 3-wire |
210 ms |
2nd order digital filter; adjustable from 0 to 100 sec |
— |
DC Voltage and DC Current
Measuring Range |
Accuracy |
Input Resistance/Voltage Drop |
Scaling |
Sampling Rate |
Input Filter |
---|---|---|---|---|---|
0 to 20 mA |
0.2% |
Voltage drop < 2 V |
Freely programmable within limits |
210 ms |
2nd order digital filter; adjustable from 0 to 100 sec |
4 to 20 mA |
0.2% |
Voltage drop < 2 V |
Freely programmable within limits |
210 ms |
2nd order digital filter; adjustable from 0 to 100 sec |
0 to 10 V |
0.1% |
Input resistance > 100 kΩ |
Freely programmable within limits |
210 ms |
2nd order digital filter; adjustable from 0 to 100 sec |
2 to 10 V |
0.1% |
Input resistance > 100 kΩ |
Freely programmable within limits |
210 ms |
2nd order digital filter; adjustable from 0 to 100 sec |
2. Relay and Binary Output
Relay Output
Operations |
Contact Rating |
---|---|
100,000 operations |
AC 230/24V; 3(0.5)A; cosφ=1 (≥ 0.6); 50Hz |
DC 24V; 3(0.5; τ=7ms)A |
|
UL60730: AC230V; 3A, D300; 30k |
|
AC/DC 24V; 3A |
|
Minimum Current |
DC 24V, 100mA |
Contact Protection |
Safety fuse 3.15AT, installed in the pole contact arm within the instrument |
Binary Output
Specification |
Details |
---|---|
Output Type |
24 V DC / 20mA logic signal |
Short-Circuit Protection |
Yes |
3. Supply
Parameter |
Specification |
---|---|
Voltage Supply |
20 to 30V AC/DC, 48 to 63Hz 110 to 240 V AC +10/-15%, 48 to 63Hz |
Power Consumption |
5 VA |
4. Environmental Influences
Parameter |
Specification |
---|---|
Ambient Temperature Range |
0°C to +55°C |
Storage Temperature Range |
-30°C to +70°C |
Temperature Error |
≤ ± 0.005% / K deviation from 23°C (resistance thermometers) ≤ ± 0.01% / K deviation from 23°C (thermocouples, current, voltage) |
Climatic Conditions |
85% relative humidity, no condensation (3K3 with extended temperature range to EN 60721) |
EMC Compliance |
EN 14597 and EN 61326 series of standards |
Interference Emission |
Class B |
Interference Immunity |
Test level for safety, control, and regulating instruments (RS) to EN 14597 |
5. Housing & Construction
Parameter |
Specification |
---|---|
Material |
Polyamide (PA 6.6) |
Screw Terminals |
0.2 to 2.5 mm² screw terminals |
Mounting |
35 mm x 7.5 mm DIN rail (EN 60715) |
Operating Position |
Vertical |
Weight |
Approx. 160 g |
Protection Rating |
IP20 (EN 60529) |