Product Description
🔹 Product Details
|
Manufacturer |
ICS Triplex |
|---|---|
|
Model/Part Number |
T3411 |
|
Description |
Monitored Digital Input Module |
🔹 Specifications
|
Attribute |
Specification |
|---|---|
|
Safetybus Power |
0.85 load units |
|
Number of Inputs |
16 (common power return) |
|
Field Power Voltage Range |
15 to 80 VDC |
|
Field Power Current (max) |
450 mA |
|
Turn-On Voltage (default) |
> 12 VDC |
|
Turn-Off Voltage (default) |
< 12 VDC |
|
Input Current (max) |
5.0 mA |
|
Turn-On Delay (max) |
10 ms |
|
Turn-Off Delay (max) |
10 ms |
|
Overvoltage Protection |
Field: 100 VDC continuousInput: 27 VDC continuous |
|
Heat Dissipation |
8.5 W / 29 BTU/hr |
|
Fusing |
Not required (internal resistor limits current to 5 mA) |
|
Isolation |
2500 V minimum (field wiring to control logic) |
|
Input Circuit Test Interval |
< 2 seconds (depends on scan time and I/O configuration) |
|
Intrinsic Safety |
Requires external barrier & threshold adjustment |
🔹 Environmental Specifications
|
Condition |
Specification |
|---|---|
|
Operating Temperature |
0°C to 60°C (32°F to 140°F) |
|
Storage Temperature |
-40°C to 85°C (-40°F to 185°F) |
|
Operating Humidity |
0–95% RH, non-condensing |
|
Vibration |
10–55 Hz: ±0.15 mm |
|
Shock (Operating) |
15 g, ½ sine wave, 11 ms |
🔹 EMI/EMC Compliance
|
Standard |
Level / Details |
|---|---|
|
IEC 801 Part 2 |
Level 3: 6 kV contact discharge |
|
IEC 801 Part 3 |
Level 3: 10 V/m, 27 MHz–500 MHz |
|
IEC 801 Part 4 |
Level 4: 2 kV, 2.5 kHz, 60 sec |
|
ANSI/IEEE C37.90 |
2.5 kV damped 1 MHz sine wave |
|
Fast Transient |
4 kV bi-directional, 10 ns rise time |
🔹 Certifications
|
Standard |
Details |
|---|---|
|
DIN V VDE 0801 |
Certified for Risk Class 5 |
|
UL/CSA Compliance |
Designed to meet UL 508 and CSA 22.2 No. 142-M1981 |
🔹 Physical Specifications
|
Dimension |
Size |
|---|---|
|
Height |
320 mm (12.6 in) |
|
Width |
32 mm (1.27 in) |
|
Depth |
257 mm (10.12 in) |
|
Weight |
1.5 kg (3.3 lbs) |