Product Description
Product Details
- Manufacturer: GENERAL ELECTRIC
- Model/Part Number: HYDRAN M2
- Description: Transformer Gas Monitoring System via FEDEX
Specifications
| Parameter | Value |
|---|---|
| Gas Monitoring | Detects hydrogen, carbon monoxide, acetylene, and ethylene to identify transformer faults |
| Moisture Measurement | Tracks moisture levels, aiding in the detection of insulation degradation |
| Expandable Sensors | Supports additional sensors for comprehensive monitoring |
| Data Transmission | Wide range of communication protocols, including Modbus® and IEC 61850, for easy SCADA integration |
| Self-Testing | Automatically performs self-checks every 15 days |
| Gas Measurement Range | 0-2000 ppm, ±10% accuracy |
| Moisture Measurement Range | 0-100% RH, ±2% accuracy |
| Operating Temperature | -40°C to +55°C |
| Power Requirements | 90–132 Vac or 180–264 Vac, 650VA max |
| Enclosure | NEMA Type 4X, IP66 rating |