Product Description
Product Overview
Field | Details |
---|---|
Manufacturer | Honeywell |
Part Number | FTA-T-03 |
Product Type | Fail-Safe Digital Output Field Termination Assembly (FTA) for Safety Manager System |
Function | Provides fail-safe digital output for safety-critical applications |
System Compatibility | Safety Manager, integrates with Fail-Safe Controller (FSC) |
Functional Specifications
Feature | Specification |
---|---|
Supported Modules | Fail-Safe Controller (FSC) digital output modules |
Channel Count | 4 channels (relay outputs) |
Output Type | Fail-safe relay contact outputs |
Safety Integrity | Designed for SIL 3 applications per IEC 61508 |
Diagnostics | Supports module diagnostics and output status monitoring |
Fail-Safe Operation | Ensures safe state (de-energized) in case of power failure or module malfunction |
Field Wiring | Screw terminals for secure connection of field wiring |
Electrical Specifications
Parameter | Specification |
---|---|
Output Voltage | 24 VDC to 230 VAC (compatible with various power supplies) |
Output Current | 2 A maximum per channel |
Power Consumption | 5 W typical |
Isolation | Galvanic isolation between channels and system |
Environmental Specifications
Parameter | Specification |
---|---|
Operating Temperature | -40°C to 70°C (-40°F to 158°F) |
Storage Temperature | -40°C to 85°C (-40°F to 185°F) |
Relative Humidity | Operating: 10% to 90% non-condensing; Storage: 5% to 95% non-condensing |
Physical Specifications
Parameter | Specification |
---|---|
Mounting | DIN rail mount, universal snap-in design |
Dimensions | 2.5 x 2.5 x 1 inches (approximate) |
Weight | 0.5 lb (approximate) |