Product Description
Product Overview
Field | Details |
---|---|
Manufacturer | Honeywell |
Part Number | FC-SDI-1624 |
Product Type | Safe Digital Input Module for Safety Manager and Experion Series C |
Function | Monitors discrete signals for safety-critical applications |
System Compatibility | Safety Manager, Experion Process Knowledge System (PKS) |
Functional Specifications
Feature | Specification |
---|---|
Input Channels | 16 channels, 24 VDC, isolated |
Input Type | Fail-to-safe, de-energizes on component failure |
Diagnostics | Self-test for logic level '0', logic level '1', and crosstalk between inputs |
Diagnostic Test Interval | Configurable, typically within system-defined interval |
Field Wiring | Supports 24 VDC out pin, current-limited for energizing field contacts |
Safety Integrity Level | SIL 3 capable (per IEC 61508) |
Redundancy | Supports redundant configurations for high availability |
Electrical Specifications
Parameter | Specification |
---|---|
Input Voltage | 24 VDC nominal (18-31 VDC operational range) |
Input Current | 7 mA per channel at 24 VDC |
Power Consumption | 5 W typical |
Isolation | Galvanic isolation between channels and system |
Current-Limited Output | 24 VDC output pin, current-limited for field contact energization |
Environmental Specifications
Parameter | Specification |
---|---|
Operating Temperature | 0°C to 60°C (32°F to 140°F) |
Storage Temperature | -40°C to 85°C (-40°F to 185°F) |
Relative Humidity | Operating: 10% to 90% non-condensing; Storage: 5% to 95% non-condensing |
Physical Specifications
Parameter | Specification |
---|---|
Dimensions | 3.2 cm x 10.7 cm x 13 cm (1.3 in x 4.2 in x 5.1 in) |
Weight | 0.3 kg (0.66 lbs) |
Mounting | Plugs into Safety Manager or Series C chassis, connects via I/O bus |