Product Description
General Information
|
Manufacturer |
Honeywell |
|---|---|
|
Model/Part Number |
CC-PAIN01 |
|
Description |
Analog Input Module |
Function
The Analog Input Module accepts high-level current input from sensing devices.
Notable Features
__Extensive self-diagnostics
__Optional redundancy
__Supplies non-incendive field power
__Fast loop scan
Technical Specifications
|
Parameter |
Specification |
|---|---|
|
Input/Output Model |
CC-PAIN01 - High-Level Analog Input |
|
IOTA Models |
CC-TAIN01 (Non-Redundant, 6_)CC-TAIN11 (Redundant, 12_) |
|
Input Type |
Current (2-wire or self-powered transmitters) |
|
Input Channels |
16 Channels (16 Single Ended) |
|
Common Mode Rejection Ratio_(DC to 60 Hz, 500 Ω source imbalance) |
70 dB |
|
A/D Converter Resolution |
16 bits |
|
Input Range |
4-20 mA (through 200 Ω) |
|
Normal Mode Rejection Ratio_(at 60 Hz) |
20 dB |
|
Normal Mode Filter Response |
Single-pole RC, -3 dB @ 6.0 Hz |
|
Maximum Normal Mode Input |
± 30 Volts |
|
Crosstalk (DC to 60 Hz, channel-to-channel) |
-60 dB |
|
Input Scan Rate |
50 ms |
|
Hardware Accuracy |
± 0.075% of full-scale (23.5°± 2°C)__± 0.15% of full-scale (0 to 60°C) |
|
Transmitter Field Power Conditioning |
Individually protected current limiting circuits for Class 1, Div 2 non-incendive interfacing. No fusing required. |
_