Product Description
General Information
| Manufacturer | Honeywell | 
|---|---|
| Model/Part Number | CC-PAIN01 | 
| Description | Analog Input Module | 
Function
The Analog Input Module accepts high-level current input from sensing devices.
Notable Features
• Extensive self-diagnostics
• Optional redundancy
• Supplies non-incendive field power
• Fast loop scan
Technical Specifications
| Parameter | Specification | 
|---|---|
| Input/Output Model | CC-PAIN01 - High-Level Analog Input | 
| IOTA Models | CC-TAIN01 (Non-Redundant, 6”)CC-TAIN11 (Redundant, 12”) | 
| Input Type | Current (2-wire or self-powered transmitters) | 
| Input Channels | 16 Channels (16 Single Ended) | 
| Common Mode Rejection Ratio (DC to 60 Hz, 500 Ω source imbalance) | 70 dB | 
| A/D Converter Resolution | 16 bits | 
| Input Range | 4-20 mA (through 200 Ω) | 
| Normal Mode Rejection Ratio (at 60 Hz) | 20 dB | 
| Normal Mode Filter Response | Single-pole RC, -3 dB @ 6.0 Hz | 
| Maximum Normal Mode Input | ± 30 Volts | 
| Crosstalk (DC to 60 Hz, channel-to-channel) | -60 dB | 
| Input Scan Rate | 50 ms | 
| Hardware Accuracy | ± 0.075% of full-scale (23.5°± 2°C) ± 0.15% of full-scale (0 to 60°C) | 
| Transmitter Field Power Conditioning | Individually protected current limiting circuits for Class 1, Div 2 non-incendive interfacing. No fusing required. | 
 
           
     
    