Output Type |
High-level constant current, 4-20mA |
Channels |
16 |
HART Capability |
Supports multivariable HART devices for status, configuration, and process control variables |
Safe-State Behavior (FAILOPT) |
Configurable per channel: HOLD LAST VALUE or SHED to SAFE VALUE (output goes to zero on failure) |
Diagnostics |
Extensive self-diagnostics for data integrity |
Redundancy |
Optional, supported via redundant IOTA (900H32-0102) |
Isolation |
Galvanic isolation (system to field) |
Field Power |
Internal or external power selection |
IOTA Models |
Non-redundant: 900H03-0102 (6-inch), Redundant: 900H32-0102 (12-inch) |
Field Connections |
Modular connectors, accepts up to 12 AWG / 2.5 mm² wire |
Power Consumption |
Derived from Series 8 power system (24V DC) |
Ambient Temperature Range |
0 to 60°C |