Product Description
General Information
|
Manufacturer |
Honeywell |
|---|---|
|
Model/Part Number |
8C-PAOHA1 (51454469-275) |
|
Description |
Analog Output with HART, Coated |
Specifications
|
Parameter |
Specification |
|---|---|
|
Input/Output Module |
8C-PAOHA1 - Analog Output with HART, Coated 8U-PAOHA1 - Analog Output with HART, Uncoated |
|
IOTA Modules |
8C-TAOXA1 - Non-Redundant, Coated, 6” 8U-TAOXA1 - Non-Redundant, Uncoated, 6” 8C-TAOXB1 - Redundant, Coated, 12” 8U-TAOXB1 - Redundant, Uncoated, 12” |
|
Output Type |
4-20 mA |
|
Output Channels |
16 |
|
Output Ripple |
< 100 mV peak-to-peak at power line frequency, across 250 Ω load |
|
Load Resistance |
50-800 Ω |
|
Voltage Rating |
24 VDC |
|
Module Current Rating |
205 mA |
|
Resolution |
± 0.05% of Full Scale |
|
Module Removal and Insertion Under Power |
Supported |
|
Calibrated Accuracy |
± 0.2% of Full Scale (25°C) including linearity |
|
Directly Settable Output Current Range |
2.9 mA to 21.1 mA |
|
Maximum Open Circuit Voltage |
22 V |
|
Response Time (DAC input code to output) |
Settles to within 1% of final value within 80 ms |
|
Gap (0 mA) of Output to Field on Switchover |
10 ms maximum (applies to Redundancy only) |
|
Agency Certifications |
Class I, Division 2, Group A, B, C, D; T4 Class I, Zone 2 AEx/ Ex nA II C T4 Class I, Division 2, Group A, B, C, D; T4 Class I, Zone 2, Ex nA II C T4 |
|
Operating Temperature |
0 to 60°C |
|
Storage Temperature |
-40 to 85°C |