Product Description
___
Product Details
|
Field |
Details |
|---|---|
|
Manufacturer |
Honeywell |
|
Model/Part Number |
2MLI-CPUU |
|
Description |
Central Processing Unit (CPU) module with power supply compatibility (AC/DC inputs) |
_
_
___
Technical Specifications (Power Supply Options)
|
Item |
2MLP-ACF1 |
2MLP-ACF2 |
2MLP-AC23 |
2MLP-DC42 |
|---|---|---|---|---|
|
Rated Input Voltage |
AC 100 _ 240V |
AC 200 _ 240V |
AC 200 _ 240V |
DC 24V |
|
Input Voltage Range |
AC 85 _ 264V |
AC 170 _ 264V |
AC 170 _ 264V |
_ |
|
Input Frequency |
50/60 Hz (47 _ 63 Hz) |
50/60 Hz (47 _ 63 Hz) |
50/60 Hz (47 _ 63 Hz) |
_ |
|
Inrush Current |
_ 20 A peak |
_ 80 A peak |
_ 80 A peak |
_ |
|
Efficiency |
_ 65% |
_ 60% |
_ 60% |
_ |
|
Input Fuse |
Built-in, UL standard (slow-blow) |
Same |
Same |
Same |
|
Instant Interruption Tolerance |
_ 10 ms |
Same |
Same |
Same |
_
_
_
Output Specifications
|
Output Channel |
Parameter |
Values |
|---|---|---|
|
Output 1 |
Voltage |
5 VDC (±2%) |
|
Current |
3.0A / 6.0A / 8.5A / 6.0A (depending on power model) |
|
|
Overcurrent Protection |
Triggers _ 3.2A / 6.6A / 9.0A / 6.6A |
|
|
Overvoltage Protection |
5.5V to 6.5V |
|
|
Output 2 |
Voltage |
24 VDC (±10%) (only on 2MLP-DC42) |
|
Current |
0.6A |
|
|
Overcurrent Protection |
_ 0.7A |
_
_
__
Relay Output Specs
|
Parameter |
Value |
|---|---|
|
Application |
RUN Contact |
|
Rated Voltage/Current |
24V DC, 0.5A |
|
Minimum Load |
5V DC, 1 mA |
|
Response Time |
OFF__N: _10 ms / ON__FF: _12 ms |
|
Mechanical Life |
_ 20 million operations |
|
Electrical Life |
_ 100,000 operations |
|
Indicator |
Output Voltage Normal: LED ON |
_
_
__
Mechanical and Electrical
|
Attribute |
Details |
|---|---|
|
Cable Spec |
0.75 _ 2 mm² |
|
Terminal Type |
RAV 1.25_3.5, RAV 2_3.5 |
|
Weight |
0.4 kg to 0.6 kg (varies by model) |
_