| Network Protocol |
PROFIBUS DP-V1 (EN 50170) |
| Node Role |
Slave only |
| Baud Rate |
Auto-detect: 9.6 kbps to 12 Mbps |
| Max I/O Data |
244 bytes input + 244 bytes output per module |
| Max Stations per Segment |
99 (with repeaters) |
| Connector |
9-pin D-sub female (isolated) |
| Cable Type |
Shielded twisted pair (Type A recommended) |
| Segment Length |
Up to 1200 m @ 9.6 kbps; 100 m @ 12 Mbps |
| Address Setting |
Rotary switches (1_125) or software |
| GSD File |
GEIC200BEM002.GSD (included with PME) |
| DP-V1 Services |
Read/Write acyclic data, alarms, diagnostics |
| Diagnostics |
Bus fault, station not ready, configuration error, module watchdog, backplane comm loss
|
| LED Indicators |
- OK (green): Module healthy - BF (red): Bus fault - SF (red): System fault - NET (green): Network active |
| Configuration |
Via Proficy Machine Edition (PME) 8.0+; GSD-based in third-party masters
|
| Firmware |
Field-upgradable via RS-232 front port or PME |
| Front Port |
RS-232 mini-DIN (for firmware update and diagnostics) |
| Isolation |
1500 V RMS network-to-backplane |
| Power Supply |
+5 V DC @ 180 mA (from backplane) |
| Power Consumption |
0.9 W maximum |
| Operating Temperature Range |
0°C to +60°C |
| Storage Temperature Range |
-40°C to +85°C |
| Humidity |
5% to 95% non-condensing |
| Vibration |
IEC 60068-2-6 (5g, 10_150 Hz) |
| Shock |
IEC 60068-2-27 (30g, 11 ms) |
| Mounting |
Snaps onto VersaMax carrier base (IC200ACCxxx) |
| Dimensions |
4.33" x 2.60" x 1.77" (110 mm x 66 mm x 45 mm) |
| Weight |
0.44 lb (0.20 kg) |
| Enclosure Rating |
IP20 |
| Revision BA Enhancements |
Firmware upgrade via RS-232, enhanced DP-V1 acyclic services, improved bus recovery, LED diagnostics, EMC immunity
|
| Standards Compliance |
IEC 61131-2, EN 50170 (PROFIBUS), CE, UL, CSA, Class I Division 2, ATEX Zone 2, RoHS 2
|