| Input Types Supported |
RTD (PT100, PT1000, Ni100, Ni120, Cu10) Thermocouple (J, K, T, E, R, S, B)
|
| Total Channels |
24 RTD or 12 Thermocouple + 12 RTD (software-configurable) |
| Input Range (RTD) |
−200°C to +850°C (PT100) |
| Input Range (T/C) |
−200°C to +1800°C (type-dependent) |
| Accuracy |
±0.3°C (RTD), ±0.5°C (T/C with CJC)
|
| Resolution |
16-bit ADC (0.05°C for RTD, 0.1°C for T/C) |
| Cold Junction Compensation |
Dual on-board PT100 RTDs (auto-redundant) |
| Update Rate |
100 ms full scan (24 channels) |
| Isolation |
500 V ch-to-ch, 1500 V to ground
|
| Fault Detection |
Open circuit, short circuit, drift, CJC failure, over/under range |
| Operating Temperature |
−40°C to +85°C |
| Storage Temperature |
−55°C to +105°C |
| Dimensions |
10.5" × 8.0" × 1.2" (Mark V/VI standard) |
| Weight |
0.92 kg (2.03 lbs) |
| Power Supply |
+5 V DC, ±15 V DC (from backplane via P1/P2) |
| Power Consumption |
< 10 W |
| Connectors |
- P1/P2: Backplane edge connectors - TB1–TB6: Removable screw terminals (24 RTD or 12 T/C + CJC) - J1/J2: CJC RTD inputs |
| LED Indicators |
6 LEDs: Power, Run, Fault, CJC OK, RTD Mode, T/C Mode
|
| Protection |
- Conformal coating (standard) - Surge (IEC 61000-4-5) - EMI/RFI shielding |
| Certifications |
CE, UL, CSA Class 1 Div 2, ATEX Zone 2, IEC 61508 SIL 2 capable
|
| Standards Compliance |
IEC 60255, API 670, IEEE C37.90, IEC 61850 GOOSE ready
|