| Voltage Supply |
+5 V DC, ±12 V DC, ±15 V DC (from backplane) |
| Operating Temperature |
_40°C to +85°C (extended industrial range) |
| Storage Temperature |
_55°C to +105°C |
| Dimensions |
10.5" _ 8.0" _ 0.6" (standard Mark V/VI form factor) |
| Weight |
0.62 kg (1.37 lbs) |
| Power Consumption |
< 7 W |
| Thyristor Bridge Support |
6-pulse or 12-pulse (auto-configurable) |
| Gate Drive Output |
6 or 12 isolated fiber-optic gate drivers (ST connectors) |
| Gate Pulse Accuracy |
±100 ns jitter, 1 µs resolution |
| Communication |
Dual Redundant 10/100 Mbps Ethernet (LAN A/B) _ supports EGD, Modbus TCP, IEEE 1588 PTP, PRP/HSR
|
| Diagnostic Features |
_ Real-time bridge current/voltage monitoring _ Phase imbalance detection _ Overcurrent / overvoltage _ Gate open/short detection _ Self-test & watchdog |
| LED Indicators |
12 LEDs: Power, Run, Fault, LAN A/B, Bridge 1_6 Status |
| Connector Type |
_ P1/P2: High-density backplane edge connectors _ P3__8: Fiber-optic ST gate outputs _ 2_ RJ45: Ethernet |
| Protection |
_ Surge (IEC 61000-4-5) _ EMI/RFI shielding _ Conformal coating (standard)
|
| Certifications |
CE, UL, CSA Class 1 Div 2, ATEX Zone 2, IEC 61508 SIL 2 capable
|
| Standards Compliance |
IEC 60255, API 670, IEEE C37.90, IEC 61850 (GOOSE), IEC 62439 (PRP/HSR)
|