| Voltage Supply |
+5 V DC, ±12 V DC, ±15 V DC (from backplane) |
| Operating Temperature |
-40°C to +85°C (extended range) |
| Storage Temperature |
-55°C to +105°C |
| Dimensions |
10.5" x 8.0" x 0.6" (standard Mark V/VI form factor) |
| Weight |
0.62 kg (1.37 lbs) |
| Power Consumption |
< 7 W |
| Thyristor Bridge Support |
6-pulse or 12-pulse (auto-configurable) |
| Gate Drive Output |
6 or 12 isolated fiber-optic gate drivers (ST-compatible) |
| Gate Pulse Accuracy |
±100 ns jitter, 1 µs resolution |
| Communication |
Dual Redundant 10/100 Mbps Ethernet (LAN A/B) – supports EGD, Modbus TCP, IEEE 1588 PTP
|
| Diagnostic Features |
- Real-time bridge current/voltage monitoring - Phase imbalance detection - Overcurrent / overvoltage - Gate open/short detection - Self-test & watchdog |
| LED Indicators |
12 LEDs: Power, Run, Fault, LAN A/B, Bridge 1–6 Status |
| Connector Type |
- P1/P2: High-density backplane edge connectors - P3–P8: Fiber-optic gate outputs (ST) - RJ45 x2: Ethernet |
| Protection |
- Surge protection (IEC 61000-4-5) - EMI/RFI shielding - Conformal coating (standard) |
| Certifications |
CE, UL, CSA Class 1 Div 2, ATEX Zone 2 (optional), IEC 61508 SIL 2 capable
|
| Standards Compliance |
IEC 60255, API 670, IEEE C37.90, IEC 61850 (GOOSE), IEC 62439 (PRP/HSR ready)
|