Skip to product information
1 of 7

Foxboro RH917GY 48 V dc Contact Sense Input Module

Foxboro RH917GY 48 V dc Contact Sense Input Module

  • Manufacturer: Foxboro

  • Product No.: RH917GY

  • Condition:1000 in stock

  • Product Type: 48 V dc Contact Sense Input Module

  • Product Origin: USA

  • Payment: T/T, Western Union

  • Weight: 185g

  • Shipping port: Xiamen

  • Warranty: 12 months

  • 24/7 Support
  • 30-Day Returns
  • Fast Shipping

Product Parameters for RH917GY (FBM207c 48 V dc Contact Sense Input Module)

📘 Product Overview

Field Details
Manufacturer Schneider Electric (Foxboro)
Part Number RH917GY
Product Type FBM207c Voltage Monitor/Contact Sense Input Module (48 V dc Contact Sense)
Function 16-channel contact sensor for 48 V dc contact sense inputs
System Compatibility Foxboro Evo Distributed Control System (DCS)
Associated PSS Document PSS 41H-2S207 (FBM207/b/c Voltage Monitor/Contact Sense Input Modules)

⚙️ Functional Specifications

Feature Specification
Input Channels 16 isolated and independent channels
Input Type Contact sense (48 V dc contact wetting from FBM207c)
Open-Circuit Voltage 48 V dc ± 15%
Short-Circuit Current 3.2 mA (typical)
Logic One (ON-State) Resistance: 1.0 kΩ (maximum)
Logic Zero (OFF-State) Resistance: 100 kΩ (minimum)
Accuracy (Pulse Count) No missing pulses for pulse rate 0 to 250 Hz
Filter/Debounce Time Configurable: No Filtering, 4, 8, 16, or 32 ms (digital filtering available with firmware version 1.25H or later)
Isolation Each channel galvanically isolated from all other channels and ground; withstands 600 V ac applied for one minute between any channel and ground or between channels (not intended for permanent connection to such voltages)
Communication Communicates with Fieldbus Communication Module (FCM) or Field Control Processor (FCP) via redundant 2 Mbps module Fieldbus
Programs Executed Discrete Input, Ladder Logic, Pulse Count, Sequence of Events (SOE) with configurable Input Filter Time
Redundancy Supports single or redundant pair configuration; redundant modules use a redundant adapter (RH926ZY) and CINR block for input validation; contact sense power diode OR'd in redundant adapter
Loop Power Supply Protection Current limited at 3.2 mA (typical)

🔋 Power Requirements

Feature Specification
Input Voltage Range 24 V dc +5%, -10% (redundant)
Power Consumption 5 W
Heat Dissipation 5 W

📏 Physical Specifications

Feature Specification
Mounting Mounts on a DIN rail mounted modular baseplate (horizontal or vertical) or 19-inch rack using a mounting kit; redundant modules must be in adjacent odd/even positions (1-2, 3-4, 5-6, or 7-8)
Weight Approximately 185 g (6.5 oz)
Dimensions (Module) - Height: 102 mm (4 in), 114 mm (4.5 in) including mounting lugs
- Width: 45 mm (1.75 in)
- Depth: 104 mm (4.11 in)
Construction Rugged extruded aluminum exterior for circuit protection
Visual Indicators LEDs on module front indicate operational status and discrete input states
Removal/Replacement Can be removed/replaced without disconnecting field device termination cabling, power, or communication cabling; redundant module replacement does not affect field input signals to the operational module

🌡️ Environmental Specifications

Parameter Operating Storage
Temperature -20 to +70°C (-4 to +158°F) -40 to +70°C (-40 to +158°F)
Relative Humidity 5 to 95% (non-condensing) 5 to 95% (non-condensing)
Altitude -300 to +3,000 m (-1,000 to +10,000 ft) -300 to +12,000 m (-1,000 to +40,000 ft)
Vibration 7.5 m/s² (0.75 g) from 5 to 500 Hz N/A
Contamination Class G3 (Harsh) per ISA S71.04, based on EIA 364-65 Class III exposure testing

Note: Environmental ranges can be extended by the enclosure type (refer to the applicable enclosure PSS).

✅ Regulatory Compliance

Certification Type Details
Electromagnetic Compatibility (EMC) - European EMC Directive 2004/108/EC (prior to April 20, 2016) and 2014/30/EU (from April 20, 2016)
- Meets EN61326-1:2013 Class A Emissions and Industrial Immunity Levels
Product Safety - UL/UL-C listed for Class I, Groups A-D, Division 2, T4 enclosure-based systems when connected to specified Foxboro DCS processor modules; meets Class 2 requirements per NEC (NFPA No.70) and CEC (CSA C22.1)
- European Low Voltage Directive 2006/95/EC (prior to April 20, 2016) and 2014/35/EU (from April 20, 2016)
- ATEX Directive 94/9/EC (prior to April 20, 2016) and 2014/34/EU (from April 20, 2016): DEMKO certified Ex nA IIC T4 for Zone 2
RoHS Compliance Complies with European RoHS Directive 2011/65/EU, including amendments 2015/863 and 2017/2102
Marine Certification ABS Type Approved and Bureau Veritas Marine certified for Environmental Category EC31
California Prop 65 Contains lead/lead compounds; warning required per www.p65warnings.ca.gov

🔌 Termination Assemblies and Cables

Feature Specification
Termination Assembly - Part Number: RH917MG (Compression), P0917MJ (Ring Lug)
- Type: Polyamide (PA), rated -20 to +70°C (-4 to +158°F)
- Certification: UL/UL-C listed for Class I, Groups A-D, Division 2, T4; DEMKO certified Ex nA IIC T4 for Zone 2; supports Class 2 limited energy circuits (60 V dc, 30 V ac, 100 VA or less) if customer equipment complies
Weight (TA) - Compression: 272 g (0.60 lb) for 127 mm (5.02 in), 317 g (0.7 lb) for 146 mm (5.75 in)
- Ring Lug: 400 g (0.90 lb) for 198 mm (7.78 in), 440 g (1.0 lb) for 216 mm (8.51 in)
Termination Cable - Type: Type 4 (37-pin male D-subminiature)
- Lengths: 0.5 to 30 m (1.6 to 98.4 ft)
- Materials: Polyurethane/PVC (-20 to +70°C) or Low Smoke Zero Halogen (LSZH, -40 to +105°C)
- Part Numbers: Refer to Table 3 (page 14) for specific cable part numbers (e.g., RH916FG for 0.5 m P/PVC, RH928BA for 0.5 m LSZH)
Field Termination Connections - Compression: 0.2 to 4 mm² (24 to 12 AWG) solid, 0.2 to 2.5 mm² stranded, 0.2 to 2.5 mm² with ferrules
- Ring Lug: #6 size connectors (9.5 mm / 0.375 in), 0.5 to 4 mm² (22 to 12 AWG)
Redundant Adapter RH926ZY (used for redundant module pairs to connect to a single TA)

🔧 Additional Features

Feature Details
Sequence of Events (SOE) Supports SOE software package (I/A Series v8.x or Control Core Services v9.0+) for event acquisition, storage, display, and reporting; supports GPS-based time synchronization for 1 ms accuracy (refer to PSS 31S-2SOE and PSS 41H-4TIMESNC)
Fieldbus Communication Accepts communication from either path (A or B) of the 2 Mbps Fieldbus; switches to active path if one fails
Calibration No calibration required for module or termination assembly
Enclosure Suitability Designed for Class G3 (harsh) environments per ISA S71.04
Wiring Recommendations For runs >305 m (1000 ft), dc excitation recommended to avoid false tripping of ac inputs; minimize coupling from adjacent signals/noise

📦 Ordering Information

Field Details
Part Number RH917GY (FBM207c Module)
Termination Assemblies - RH917MG (Compression)
- P0917MJ (Ring Lug)
Redundant Adapter RH926ZY (for redundant configurations)
Termination Cables Type 4 cables, lengths 0.5 to 30 m (refer to Table 3, page 14)
Related PSS Documents - PSS 41H-2SOV (I/O Subsystem Overview)
- B0400FA (Subsystem User’s Guide)
- PSS 41H-2SBASPLT (Baseplates)
- PSS 41H-2CERTS (Certifications)
- PSS 41S-3FCPICS (FCP280 Control Software)

 

View full details

Product Description

Product Parameters for RH917GY (FBM207c 48 V dc Contact Sense Input Module)

📘 Product Overview

Field Details
Manufacturer Schneider Electric (Foxboro)
Part Number RH917GY
Product Type FBM207c Voltage Monitor/Contact Sense Input Module (48 V dc Contact Sense)
Function 16-channel contact sensor for 48 V dc contact sense inputs
System Compatibility Foxboro Evo Distributed Control System (DCS)
Associated PSS Document PSS 41H-2S207 (FBM207/b/c Voltage Monitor/Contact Sense Input Modules)

⚙️ Functional Specifications

Feature Specification
Input Channels 16 isolated and independent channels
Input Type Contact sense (48 V dc contact wetting from FBM207c)
Open-Circuit Voltage 48 V dc ± 15%
Short-Circuit Current 3.2 mA (typical)
Logic One (ON-State) Resistance: 1.0 kΩ (maximum)
Logic Zero (OFF-State) Resistance: 100 kΩ (minimum)
Accuracy (Pulse Count) No missing pulses for pulse rate 0 to 250 Hz
Filter/Debounce Time Configurable: No Filtering, 4, 8, 16, or 32 ms (digital filtering available with firmware version 1.25H or later)
Isolation Each channel galvanically isolated from all other channels and ground; withstands 600 V ac applied for one minute between any channel and ground or between channels (not intended for permanent connection to such voltages)
Communication Communicates with Fieldbus Communication Module (FCM) or Field Control Processor (FCP) via redundant 2 Mbps module Fieldbus
Programs Executed Discrete Input, Ladder Logic, Pulse Count, Sequence of Events (SOE) with configurable Input Filter Time
Redundancy Supports single or redundant pair configuration; redundant modules use a redundant adapter (RH926ZY) and CINR block for input validation; contact sense power diode OR'd in redundant adapter
Loop Power Supply Protection Current limited at 3.2 mA (typical)

🔋 Power Requirements

Feature Specification
Input Voltage Range 24 V dc +5%, -10% (redundant)
Power Consumption 5 W
Heat Dissipation 5 W

📏 Physical Specifications

Feature Specification
Mounting Mounts on a DIN rail mounted modular baseplate (horizontal or vertical) or 19-inch rack using a mounting kit; redundant modules must be in adjacent odd/even positions (1-2, 3-4, 5-6, or 7-8)
Weight Approximately 185 g (6.5 oz)
Dimensions (Module) - Height: 102 mm (4 in), 114 mm (4.5 in) including mounting lugs
- Width: 45 mm (1.75 in)
- Depth: 104 mm (4.11 in)
Construction Rugged extruded aluminum exterior for circuit protection
Visual Indicators LEDs on module front indicate operational status and discrete input states
Removal/Replacement Can be removed/replaced without disconnecting field device termination cabling, power, or communication cabling; redundant module replacement does not affect field input signals to the operational module

🌡️ Environmental Specifications

Parameter Operating Storage
Temperature -20 to +70°C (-4 to +158°F) -40 to +70°C (-40 to +158°F)
Relative Humidity 5 to 95% (non-condensing) 5 to 95% (non-condensing)
Altitude -300 to +3,000 m (-1,000 to +10,000 ft) -300 to +12,000 m (-1,000 to +40,000 ft)
Vibration 7.5 m/s² (0.75 g) from 5 to 500 Hz N/A
Contamination Class G3 (Harsh) per ISA S71.04, based on EIA 364-65 Class III exposure testing

Note: Environmental ranges can be extended by the enclosure type (refer to the applicable enclosure PSS).

✅ Regulatory Compliance

Certification Type Details
Electromagnetic Compatibility (EMC) - European EMC Directive 2004/108/EC (prior to April 20, 2016) and 2014/30/EU (from April 20, 2016)
- Meets EN61326-1:2013 Class A Emissions and Industrial Immunity Levels
Product Safety - UL/UL-C listed for Class I, Groups A-D, Division 2, T4 enclosure-based systems when connected to specified Foxboro DCS processor modules; meets Class 2 requirements per NEC (NFPA No.70) and CEC (CSA C22.1)
- European Low Voltage Directive 2006/95/EC (prior to April 20, 2016) and 2014/35/EU (from April 20, 2016)
- ATEX Directive 94/9/EC (prior to April 20, 2016) and 2014/34/EU (from April 20, 2016): DEMKO certified Ex nA IIC T4 for Zone 2
RoHS Compliance Complies with European RoHS Directive 2011/65/EU, including amendments 2015/863 and 2017/2102
Marine Certification ABS Type Approved and Bureau Veritas Marine certified for Environmental Category EC31
California Prop 65 Contains lead/lead compounds; warning required per www.p65warnings.ca.gov

🔌 Termination Assemblies and Cables

Feature Specification
Termination Assembly - Part Number: RH917MG (Compression), P0917MJ (Ring Lug)
- Type: Polyamide (PA), rated -20 to +70°C (-4 to +158°F)
- Certification: UL/UL-C listed for Class I, Groups A-D, Division 2, T4; DEMKO certified Ex nA IIC T4 for Zone 2; supports Class 2 limited energy circuits (60 V dc, 30 V ac, 100 VA or less) if customer equipment complies
Weight (TA) - Compression: 272 g (0.60 lb) for 127 mm (5.02 in), 317 g (0.7 lb) for 146 mm (5.75 in)
- Ring Lug: 400 g (0.90 lb) for 198 mm (7.78 in), 440 g (1.0 lb) for 216 mm (8.51 in)
Termination Cable - Type: Type 4 (37-pin male D-subminiature)
- Lengths: 0.5 to 30 m (1.6 to 98.4 ft)
- Materials: Polyurethane/PVC (-20 to +70°C) or Low Smoke Zero Halogen (LSZH, -40 to +105°C)
- Part Numbers: Refer to Table 3 (page 14) for specific cable part numbers (e.g., RH916FG for 0.5 m P/PVC, RH928BA for 0.5 m LSZH)
Field Termination Connections - Compression: 0.2 to 4 mm² (24 to 12 AWG) solid, 0.2 to 2.5 mm² stranded, 0.2 to 2.5 mm² with ferrules
- Ring Lug: #6 size connectors (9.5 mm / 0.375 in), 0.5 to 4 mm² (22 to 12 AWG)
Redundant Adapter RH926ZY (used for redundant module pairs to connect to a single TA)

🔧 Additional Features

Feature Details
Sequence of Events (SOE) Supports SOE software package (I/A Series v8.x or Control Core Services v9.0+) for event acquisition, storage, display, and reporting; supports GPS-based time synchronization for 1 ms accuracy (refer to PSS 31S-2SOE and PSS 41H-4TIMESNC)
Fieldbus Communication Accepts communication from either path (A or B) of the 2 Mbps Fieldbus; switches to active path if one fails
Calibration No calibration required for module or termination assembly
Enclosure Suitability Designed for Class G3 (harsh) environments per ISA S71.04
Wiring Recommendations For runs >305 m (1000 ft), dc excitation recommended to avoid false tripping of ac inputs; minimize coupling from adjacent signals/noise

📦 Ordering Information

Field Details
Part Number RH917GY (FBM207c Module)
Termination Assemblies - RH917MG (Compression)
- P0917MJ (Ring Lug)
Redundant Adapter RH926ZY (for redundant configurations)
Termination Cables Type 4 cables, lengths 0.5 to 30 m (refer to Table 3, page 14)
Related PSS Documents - PSS 41H-2SOV (I/O Subsystem Overview)
- B0400FA (Subsystem User’s Guide)
- PSS 41H-2SBASPLT (Baseplates)
- PSS 41H-2CERTS (Certifications)