Product Description
Product Overview
Field | Details |
---|---|
Manufacturer | Schneider Electric (Foxboro) |
Part Number | P0926GV |
Product Type | FBM231 Field Device System Integrator Module, Four Serial Ports, Redundant |
Function | Provides serial interface between dual-ported field I/O devices and Foxboro DCS |
System Compatibility | EcoStruxure Foxboro DCS, Standard 200 Series Subsystem |
Associated Document | PSS 41H-2S231 |
Functional Specifications
Feature | Specification |
---|---|
Interface | Four serial I/O ports, individually configurable for RS-232, RS-422, or RS-485 |
Port Configuration | Ports 1, 2, 3, and/or 4 can form a single logical port with redundant cables for dual-ported devices |
Bus Characteristics | - RS-232: DB-25 cable to customer-supplied device/modem/converter - RS-422: 4-wire medium - RS-485: Twisted-pair shielded copper cable with single conductor pair |
Communication | Asynchronous, direct connect (RS-232); 8-bit characters; odd, even, or no parity; 1 or 2 stop bits |
Transmission Rate | 300, 600, 1200, 2400, 4800, 9600, 19200, 38400, 57600, 115200 baud |
I/O Capacity | Up to 64 devices (RS-485, 16 per port) or 4 direct-connect RS-232/RS-422 devices; up to 2000 DCI point connections |
Data Types | 2-byte or 4-byte signed/unsigned integers, 4-byte IEEE single-precision floating values, binary values; driver-dependent conversions |
Fastest ECB Block Period | 500 ms |
Redundancy | Pair of FBM231 modules (Master and Tracker); automatic role switching on fault detection (e.g., heartbeat) or manual via SMDH |
I/O Drivers | Downloadable software drivers from protocol library; custom drivers available |
Control Blocks | Supports DCI blocks: BIN, BINR, BOUT, IIN, IOUT, PAKIN, PAKOUT, PLSOUT, RIN, RINR, ROUT, STRIN, STROUT |
Channel Isolation | Galvanically isolated, referenced to earth; withstands 600 V AC for 1 minute (not for permanent connection) |
Fieldbus Communication | Interfaces with FCM100Et, FCM100E, FCP270, or FCP280 via redundant 2 Mbps module Fieldbus |
Visual Indicators | LEDs for operational status, communication activity (transmit/receive per port), and Master/Tracker status |
Physical Specifications
Feature | Specification |
---|---|
Mounting | Modular Baseplate (DIN rail or 19-inch rack); redundant FBM231s in adjacent odd/even positions (1-2, 3-4, 5-6, or 7-8) |
Dimensions (Module) | - Height: 102 mm (4 in), 114 mm (4.5 in) with mounting lugs - Width: 45 mm (1.75 in) - Depth: 104 mm (4.11 in) |
Mass (Module) | 284 g (10 oz) approximate |
Construction | Rugged extruded aluminum exterior |
Termination Assembly | - Part Numbers: RH926GH (compression screw, supersedes P0926GH), P0926PA (ring lug) - Mass: 272 g (0.6 lb) for RH926GH, 363 g (0.8 lb) for P0926PA - Features: 32/35 mm DIN rail mount, three-tier terminals for RS-422/RS-485, four DB-25 connectors for RS-232, switch-selectable termination resistors |
Cables | - FBM231 to TA: Type 5, 1 m (3.2 ft) to 5 m (16.4 ft) - RS-232 (DB-25): Up to 15 m (50 ft) - RS-422/RS-485: Up to 1200 m (3937 ft) |
Termination Cables | LSZH, Type 5: RH928AW (1 m), RH928AX (2 m), RH928AY (3 m), RH928AZ (5 m) |
Environmental Specifications
Parameter | Specification |
---|---|
Operating Temperature | - Rev A-L: -20 to +70°C (-4 to +158°F) - Rev M+: 0 to +70°C (32 to +158°F) |
Storage Temperature | -40 to +70°C (-40 to +158°F) |
Relative Humidity | 5 to 95% (noncondensing) |
Contamination | Class G3 (Harsh) per ISA Standard S71.04, EIA Standard 364-65 Class III |
Regulatory Compliance
Certification Type | Details |
---|---|
EMC | European EMC Directive 2014/30/EU; EN61326-1:2013 Class A Emissions, Industrial Immunity Levels |
Product Safety | - UL/UL-C: Class I, Groups A-D, Division 2, T4; Class 2 circuits per NFPA 70, CSA C22.1 - ATEX: Ex nA IIC T4 for Zone 2 (per B0400FA) - Conditions: Per Standard and Compact 200 Series Subsystem User’s Guide (B0400FA) |
Marine Certification | ABS Type Approved, Bureau Veritas Marine certified for EC31 |
California Prop 65 | Contains lead/lead compounds (cancer/reproductive harm risk) |
Power Specifications
Feature | Specification |
---|---|
Input Voltage | 24 V DC +5%, -10% (redundant) |
Consumption | 7 W (maximum) per module |
Heat Dissipation | 7 W (maximum) per module |
Additional Features
Feature | Details |
---|---|
Calibration | Not required for module or TA |
Configuration | FDSI configurator with XML-based device configuration files for port setup (baud rate, parity) and device-specific parameters (scan rate, data address) |
Operations | Supports up to 2000 analog or 64000 digital I/O values; data stored in module database for Foxboro DCS integration |
Reliability | High availability via redundancy; hot-swappable without disrupting I/O signals |
Ordering Information
Field | Details |
---|---|
Part Number | P0926GV (FBM231 Module) |
Related Components | - TAs: RH926GH (compression), P0926PA (ring lug) - Cables: RH928AW (1 m), RH928AX (2 m), RH928AY (3 m), RH928AZ (5 m) |
Related Documents | - PSS 31H-2SOV: Standard 200 Series Subsystem Overview - PSS 31H-2CERTS: Agency Certifications - PSS 31H-2SBASPLT: Modular Baseplates |