Product Description
Product Parameters for P0917QW Termination Assembly
📘 Product Overview
Field | Details |
---|---|
Manufacturer | Foxboro (by Schneider Electric) |
Part Number | P0917QW (superseded by RH917QW) |
Product Type | Termination Assembly (TA) for FBM205 |
Function | Interfaces four 0 to 20 mA analog input channels and four 0 to 20 mA analog output channels for FBM205 |
Associated FBM | FBM205 (Redundant 0 to 20 mA I/O Interface Module) |
System Compatibility | Foxboro Evo Process Automation System, Standard 200 Series FBM Subsystem |
⚙️ Functional Specifications
Feature | Specification |
---|---|
Signal Inputs | |
- Type | 0 to 20 mA dc analog inputs (4 channels) |
- Number of Channels | 4 group-isolated input channels |
- Input Impedance | 60 Ω nominal (resistor in redundant adapter) |
Signal Outputs | |
- Type | 0 to 20 mA dc analog outputs (4 channels) |
- Number of Channels | 4 group-isolated output channels |
- Output Load | 750 Ω maximum |
Special Features | Includes built-in bypass jacks for each output channel; accepts bypass plug from VA Series Output Bypass Station (Foxboro P/N P0900HJ) or other external 20 mA sources |
Connection Type | Compression terminals; connects to FBM via 25-pin male D-subminiature termination cable through redundant adapter (RH916NN) |
Supported Cables | Type 1 (P/PVC or LSZH): RH916DA–RH916DJ (P/PVC) or RH928AA–RH928AK (LSZH); lengths from 0.5 m (1.6 ft) to 30 m (98.4 ft) |
Cable Material | Polyurethane (P/PVC) or Low Smoke Zero Halogen (LSZH) |
Redundant Adapter | RH916NN (supersedes P0916NN) required for redundant FBM205 configuration |
Power Requirements | None (passive device; power supplied by FBM205) |
Calibration | No calibration required |
🔌 Physical Specifications
Feature | Specification |
---|---|
Material | Polyamide (PA) |
Mass | Approximately 159 g (0.35 lb) for compression type |
Dimensions | Not explicitly detailed for P0917QW; typical for FBM TAs: Width ~267–286 mm, Height ~125 mm (refer to P0917JP for similar TA dimensions) |
Mounting | DIN rail (32 mm or 35 mm) |
Terminal Blocks | Inputs: 3 tiers, 4 positions; Outputs: 3 tiers, 4 positions; Output Bypass Jacks: 4 |
Field Termination Connections | Compression: 0.2 to 4 mm² (24 to 12 AWG) solid, 0.2 to 2.5 mm² stranded, 0.2 to 2.5 mm² with/without ferrules |
🌡️ Environmental Specifications
Parameter | Specification |
---|---|
Operating Temperature | -20 to +70°C (-4 to +158°F) (PA material) |
Storage Temperature | -40 to +70°C (-40 to +158°F) |
Relative Humidity | 5 to 95% (non-condensing) |
Operating Altitude | -300 to +3,000 m (-1,000 to +10,000 ft) |
Storage Altitude | -300 to +12,000 m (-1,000 to +40,000 ft) |
Contamination | Class G3 (Harsh) per ISA S71.04; EIA Standard 364-65, Class III |
Vibration | 0.75 m/s² (5 to 500 Hz) |
✅ Regulatory Compliance
Certification Type | Details |
---|---|
Certification Types | Type 4, Type 5 (see definitions below) |
Type 4 Certification | All field circuits are Class 2 limited energy (60 V dc, 30 V ac, 100 VA or less) if customer-supplied equipment meets Class 2 limits |
Type 5 Certification | TA and its field circuitry are for use in ordinary (non-hazardous) locations only |
Note | DEMKO certification (Ex nA IIC T4 for Zone 2) does not apply to P0917QW/RH917QW |
EMC Compliance | Meets European EMC Directive 2014/30/EU; EN61326-1:2013 Class A Emissions and Industrial Immunity Levels |
RoHS Compliance | Complies with European RoHS Directive 2011/65/EU |
📦 Ordering Information
Field | Details |
---|---|
Part Number | P0917QW (superseded by RH917QW) |
Associated FBM | FBM205 (Redundant 0 to 20 mA I/O Interface Module) |
Other TAs for FBM205 | RH916XL (compression), P0917JP (ring lug) |
Redundant Adapter | RH916NN (supersedes P0916NN) |
Conditions of Use | Must be installed and used as specified in the Standard and Compact 200 Series Subsystem User’s Guide (B0400FA) |