Product Parameters for P0917MG (Termination Assembly)
📘 Product Overview
| Field | Details |
|---|---|
| Manufacturer | Foxboro (by Schneider Electric) |
| Part Number | P0917MG (superseded by RH917MG) |
| Product Type | Termination Assembly (Compression Terminals) |
| Function | Connects field I/O signals to FBM207c module for 16-channel contact sense inputs at 48 V DC |
| System Compatibility | Foxboro Evo Standard 200 Series Subsystem, used with FBM207c (RH917GY, supersedes P0917GY) |
| Associated PSS Document | PSS 31H-2S207 |
⚙️ Functional Specifications
| Feature | Specification |
|---|---|
| Input Signal | 16-channel contact sense, 48 V DC contact wetting from FBM207c |
| Isolation | Channel isolation provided by FBM207c (each channel galvanically isolated from others and ground) |
| Open-Circuit Voltage | 48 V DC ± 15% (provided by FBM207c) |
| Short-Circuit Current | 3.2 mA (typical) |
| Logic One (On-State) | Resistance: 1.0 kΩ (maximum) |
| Logic Zero (Off-State) | Resistance: 100 kΩ (minimum) |
| Termination Type | Compression terminals |
| Cable Type | Type 4 (37-pin male D-subminiature connector) |
| Cable Lengths | Up to 30 m (98 ft), available in lengths: 0.5 m, 1.0 m, 2.0 m, 3.0 m, 5.0 m, 10.0 m, 15.0 m, 20.0 m, 25.0 m, 30.0 m (see Table 2, Page 12–13) |
| Cable Materials | - Polyurethane/PVC: -20 to +70°C (-4 to +158°F) - Low Smoke Zero Halogen (LSZH): -40 to +105°C (-40 to +221°F) |
| Cable Part Numbers | - P/PVC: RH916FG, RH916FH, RH931RQ, RH916FJ, RH916FK, RH916FL, RH916FM, RH916FN, RH916FP, RH916FQ - LSZH: RH928BA, RH928BB, RH928BC, RH928BD, RH928BE, RH928BF, RH928BG, RH928BH, RH928BJ, RH928BK |
| Redundancy Support | Compatible with single or redundant FBM207c modules via redundant adapter (RH926ZY, supersedes P0926ZY) |
| Field Wiring | - Accepted Sizes: Solid/Stranded: 0.2 to 4 mm² / 0.2 to 2.5 mm², AWG 24 to 12 - Stranded with Ferrules: 0.2 to 2.5 mm² (with or without plastic collar) |
| Terminal Blocks | - Inputs: 2 tiers, 16 positions - Excitation: 2 tiers, 4 positions |
📏 Physical Specifications
| Feature | Specification |
|---|---|
| Mounting | DIN rail mount, compatible with 32 mm (1.26 in) and 35 mm (1.38 in) DIN rails |
| Dimensions | - Height: 127 mm (5.02 in) or 146 mm (5.75 in) (Page 14, exact variant not specified for P0917MG) - Width and Depth: Not specified, typical for compression TAs |
| Weight | - 272 g (0.60 lb) for 127 mm version - 317 g (0.70 lb) for 146 mm version (Page 8) |
| Material | Polyamide (PA) |
| Color | Dark blue (discrete family group) |
🌡️ Environmental Specifications
| Parameter | Specification |
|---|---|
| Operating Temperature | -20 to +70°C (-4 to +158°F) |
| Operating Humidity | 5 to 95% (noncondensing) |
| Storage Temperature | -40 to +70°C (-40 to +158°F) |
| Storage Humidity | 5 to 95% (noncondensing) |
| Contamination | Class G3 (harsh) per ISA S71.04 |
| Vibration | 7.5 m/s² from 5 to 500 Hz |
✅ Regulatory Compliance
| Certification Type | Details |
|---|---|
| EMC | Complies with European EMC Directive 2004/108/EC (prior to April 20, 2016) and 2014/30/EU (from April 20, 2016); meets EN61326-1:2013 Class A Emissions and Industrial Immunity Levels |
| RoHS | Complies with European RoHS Directive 2011/65/EU |
| Product Safety | - UL/UL-C listed as suitable for Class I, Groups A-D, Division 2, T4 hazardous locations (Type 1) - UL/UL-C listed as associated apparatus for non-incendive field circuits in Class I, Groups A-D, Division 2 (Type 2) when connected to specified 200 Series FBMs (per B0400FA) - DEMKO certified EEx nA IIC T4 for Zone 2 (Type 1) - DEMKO certified as associated apparatus for Group IIC, Zone 2 field circuits (Type 2) - Field circuits meet Class 2 limited energy (60 V DC, 30 V AC, 100 VA or less) if customer equipment complies |
| Marine Certification | ABS Type Approved and Bureau Veritas Marine certified for Environmental Category EC31 |
| Conditions of Use | Per Standard and Compact 200 Series Subsystem User’s Guide (B0400FA) |
🔧 Additional Features
| Feature | Details |
|---|---|
| Signal Conditioning | No additional signal conditioning (passive TA, relies on FBM207c for contact wetting) |
| Connection | Connects to FBM207c baseplate via Type 4 termination cable; redundant adapter (RH926ZY) for redundant FBM207c pair |
| Wiring Notes | - No load required for input channel operation - DC inductive loads may require a diode |
| Compatibility | Supports FBM207c (48 V DC contact sense); not compatible with FBM207 or FBM207b |
📦 Ordering Information
| Field | Details |
|---|---|
| Part Number | P0917MG (superseded by RH917MG) |
| Superseded Part Numbers | P0917MF |
| Related Components | - FBM207c Module: RH917GY (supersedes P0917GY) - Redundant Adapter: RH926ZY (supersedes P0926ZY) - Termination Cables: See Table 2 (Page 12–13) - Alternative TA: P0917MJ (ring lug, supersedes P0917MH) |
| Related PSS Documents | - PSS 31H-2SOV: Standard 200 Series Subsystem Overview - PSS 31H-2CERTS: Agency Certifications - PSS 31H-2SBASPLT: Standard 200 Series Baseplates |