Product Description
General Information
|
Field |
Details |
|---|---|
|
Manufacturer |
Foxboro |
|
Model Number |
FBM206 P0916JQ |
|
Module Type |
Pulse Input Module |
|
Description |
8-channel pulse input module accepting 2-wire pulse signals from various sensors (e.g., turbine meters, vortex, solid-state/electromechanical contacts). |
Environmental Specifications
|
Parameter |
Specification |
|---|---|
|
Operating Temperature |
-20 to +70°C (-4 to +158°F) |
|
Storage Temperature |
-40 to +70°C (-40 to +158°F) |
|
Operating Humidity |
5 to 95% RH (non-condensing) |
|
Storage Humidity |
5 to 95% RH (non-condensing) |
|
Operating Altitude |
-300 to +3,000 m (-1,000 to +10,000 ft) |
|
Storage Altitude |
-300 to +12,000 m (-1,000 to +40,000 ft) |
|
Contamination |
Class G3 (Harsh) per ISA S71.04 / EIA 364-65 Class III |
|
Vibration |
7.5 m/s² (0.75 g), 5 to 500 Hz |
Physical Specifications
|
Component |
Specification |
|---|---|
|
Mounting |
On modular baseplate (DIN rail, 19” rack, or 100 Series conversion structure) |
|
Module Weight |
Approx. 284 g (10 oz) |
|
TA Weight - Compression |
Approx. 181 g (0.40 lb) |
|
TA Weight - Ring Lug |
Approx. 249 g (0.55 lb) |
|
Module Dimensions |
102 mm H × 45 mm W × 104 mm D (114 mm H incl. lugs) |
|
Termination Assembly |
DIN rail mountable; compatible with 32 mm and 35 mm rails |
|
Construction - TA |
Polyamide (PA); Compression or Ring Lug types |
Termination and Cabling
|
Feature |
Details |
|---|---|
|
Cable Length |
Up to 30 m (98 ft) |
|
Cable Materials |
Polyurethane or LSZH |
|
Termination Cable Type |
Type 1 |
|
Baseplate to TA Connection |
37-pin D-sub (Baseplate) ↔ 25-pin D-sub (TA) |
|
Compression-Type Wiring Sizes |
0.2–4 mm² (solid), 0.2–2.5 mm² (stranded), 24–12 AWG |
|
Stranded with Ferrules |
0.2–2.5 mm² with/without plastic collar |
|
Ring Lug Type Wiring Sizes |
#6 connectors, 0.5–4 mm², 22–12 AWG |
Ordering Information
|
Component |
Part Number |
Notes |
|---|---|---|
|
FBM206 Module |
RH916CQ (replaces P0916CQ) |
8-channel pulse input module |
|
FBM206b Module |
RH927AB (replaces P0927AB) |
4 pulse in + 4 analog out combo |
|
Termination Assemblies |
Refer to functional specs – see page referenced |
Includes compression and ring lug options |