Product Description
📘 Product Overview
Field | Details |
---|---|
Manufacturer | Schneider Electric (Foxboro) |
Model Number | FBM204 P0916DC |
Product Type | 0 to 20 mA I/O Module |
Function | Provides four 20 mA dc analog input channels and four 20 mA dc analog output channels |
System Compatibility | Interfaces with Foxboro DCS via redundant 2 Mbps module Fieldbus; compatible with 200 Series baseplates and 100 Series upgrades |
Included Components | FBM204 module; requires separate Termination Assembly (TA) and cables |
⚙️ Hardware Specifications
Feature | Specification |
---|---|
Input Channels | 4 isolated and independent 20 mA dc analog input channels |
Output Channels | 4 isolated and independent 20 mA dc analog output channels |
Input/Output Range | 0 to 20.4 mA dc (nominal) |
Input Accuracy | ±0.03% of span (includes linearity) |
Output Accuracy | ±0.03% of span (includes linearity) |
Accuracy Temperature Coefficient | ±50 ppm/°C |
Input Signal A/D Conversion | Independent Sigma-Delta converter per channel (new reading every 25 ms) |
Input Channel Impedance | 61.5 Ω nominal |
Integration Period | Software configurable |
Common Mode Rejection | >100 dB at 50 or 60 Hz |
Normal Mode Rejection | >95 dB at 50 or 60 Hz |
Output Load | 750 Ω maximum |
Output Processing Delay | 30 ms maximum |
Output Resolution | 13 bits |
Input Channel Isolation | Galvanically isolated; withstands 600 V AC for 1 minute (not for permanent connection) |
Loop Power Supply Protection (Input) | Galvanically isolated, current limited (<30 mA, ~100 mA if shorted), voltage regulated |
Loop Power Supply Protection (Output) | Galvanically isolated, current limited (~25 mA, up to 35 mA if FET shorts), voltage regulated |
Field Device Cabling Distance (Input) | Depends on compliance voltage (20.2 V dc at 20.4 mA), wire gauge, and field device voltage drop |
Field Device Cabling Distance (Output) | Depends on compliance voltage (19.6 V dc at 20.4 mA), wire gauge, and field device voltage drop |
HART Compatibility | Electrically compatible with standard HART signals; requires 200 Ω in-line resistor (RH902VY) for FoxCom/HART transmitters |
Visual Indicators | Red and green LEDs for module status |
Construction | Rugged extruded aluminum exterior |
🔌 Power Requirements
Feature | Specification |
---|---|
Input Voltage Range (Redundant) | 24 V DC +5%, -10% |
Consumption | 7 W (maximum) |
Heat Dissipation | 3.5 W (maximum) |
🌡️ Environmental Specifications
Parameter | Specification |
---|---|
Operating Temperature | Module and TA (PA): -20 to +70°C (-4 to +158°F) |
Storage Temperature | -20 to +70°C (-4 to +158°F) |
Relative Humidity | 5 to 95% (non-condensing) |
Altitude (Operating) | -300 to +3,000 m (-1,000 to +10,000 ft) |
Altitude (Storage) | -300 to +12,000 m (-1,000 to +40,000 ft) |
Vibration | 7.5 m/s² (0.75 g) from 5 to 500 Hz |
Contamination | Class G3 (harsh) per ISA S71.04, tested per EIA 364-65, Class III |
✅ Regulatory Compliance
Standard | Details |
---|---|
EMC | European EMC Directive 2004/108/EC (pre-Apr 2016), 2014/30/EU (post-Apr 2016); EN61326-1:2013 Class A Emissions, Industrial Immunity |
Product Safety (UL) | UL/UL-C listed for Class I, Groups A-D, Division 2, T4; Class 2 per NEC (NFPA No.70) and CSA C22.1 |
Product Safety (Europe) | Low Voltage Directive 2006/95/EC (pre-Apr 2016), 2014/35/EU (post-Apr 2016); ATEX 94/9/EC (pre-Apr 2016), 2014/34/EU (post-Apr 2016); DEMKO Ex nA IIC T4 for Zone 2 (except TA RH917QW) |
RoHS Compliance | Complies with European RoHS Directive 2011/65/EU, including 2015/863, 2017/2102 |
Marine Certification | ABS Type Approved; Bureau Veritas certified for Environmental Category EC31 |
🛠️ Installation & Configuration
Feature | Details |
---|---|
Mounting | Mounts on DIN rail or 19-inch rack modular baseplate (4 or 8 FBMs); supports 100 Series conversion structures |
Termination Assemblies | DIN rail-mounted: compression (PA: RH916XK, RH917QW), ring lug (PVC: P0916AH) |
Auto-Detection | Communicates via redundant 2 Mbps Fieldbus; auto-switches to active path |
Configuration | Analog I/O application program with configurable Conversion Time, Fail-Safe (Hold/Fallback), and Output Fail-Safe Fallback Data; supports DPIDA control blocks |
Calibration | Not required |
Removal/Replacement | Can be removed/replaced without disconnecting field wiring, power, or communication cables |
📡 Termination Assemblies and Cables
Feature | Specification |
---|---|
TA Types | Compression (PA: RH916XK, RH917QW); Ring Lug (PVC: P0916AH) |
TA Features | RH917QW includes bypass jacks for output channels (compatible with Foxboro P0900HJ Output Bypass Station) |
TA Wiring (Compression) | Solid/Stranded: 0.2 to 4 mm² / 0.2 to 2.5 mm² (24 to 12 AWG); Ferrules: 0.2 to 2.5 mm² |
TA Wiring (Ring Lug) | #6 connectors (0.375 in); 0.5 to 4 mm² (22 to 12 AWG) |
TA Certification | Type 1 (RH916XK, P0916AH): UL/UL-C Class I, Div 2, T4; DEMKO Ex nA IIC T4 (Zone 2); Type 4/5 (RH917QW): Class 2 limited energy, non-hazardous locations only |
Cable Types | Type 1 (P/PVC: -20 to +80°C; LSZH: -40 to +105°C) |
Cable Lengths | Up to 30 m (98 ft) |
Cable Connectors | Baseplate: 37-pin D-sub; TA: 25-pin D-sub |
Example Cable Part Numbers | 2.0 m: RH931RM (P/PVC), RH928AC (LSZH); 3.0 m: RH916DC (P/PVC), RH928AD (LSZH); 30 m: RH916DJ (P/PVC), RH928AK (LSZH) |
🔧 Functional Specifications
Feature | Details |
---|---|
Input Signal | Accepts 4 to 20 mA transmitters or self-powered 20 mA sources |
Output Signal | Drives external loads with 0 to 20 mA output |
Process I/O Communications | Redundant 2 Mbps Fieldbus with FCM or FCP; auto-switches to active path |
100 Series Upgrade | Replaces 100 Series FBM04; supports TA or Termination Assembly Adapter (TAA) for existing wiring |
📦 Ordering Information
Field | Details |
---|---|
Model Number | FBM204 (RH914SY, likely supersedes P0916DC) |
Includes | FBM204 module (TA and cables ordered separately) |
TA Part Numbers | Compression: RH916XK, RH917QW; Ring Lug: P0916AH |