Product Description
Product Parameters for FBM201 RH914SQ
General Description
-
Manufacturer: Schneider Electric (Foxboro)
-
Model Number: FBM201 (Part Number: RH914SQ, supersedes P0914SQ)
-
Product Type: Analog Input Module
-
Function: Provides eight analog input channels for 0 to 20 mA dc signals from analog sensors (e.g., 4 to 20 mA transmitters or self-powered 20 mA sources).
-
System Compatibility:
- Interfaces with the Foxboro Evo Process Automation System via a redundant 2 Mbps module Fieldbus.
- Electrically compatible with standard HART signals.
- Mounts on a modular baseplate accommodating up to four or eight FBMs, compatible with DIN rail or rack mounting.
Hardware Specifications
-
Input Channels: 8 isolated and independent channels
-
Input Range: 0 to 20 mA dc
-
Input Channel Impedance: 61.5 Ω nominal
-
Analog Accuracy (Includes Linearity): ±0.03% of span
-
Accuracy Temperature Coefficient: ±50 ppm/°C
-
Input Signal A/D Conversion: Each channel uses an independent Sigma-Delta converter, providing a new reading every 25 ms
-
Integration Period: Software configurable
-
Common Mode Rejection: >100 dB at 50 or 60 Hz
-
Normal Mode Rejection: >95 dB at 50 or 60 Hz
-
Input Channel Isolation:
- Each channel is galvanically isolated from other channels and ground.
- Withstands 600 V ac applied for one minute between any channel and ground or between channels (not intended for permanent connection to such voltages).
-
Loop Power Supply Protection:
- Each channel is galvanically isolated, current limited, and voltage regulated.
- Analog inputs limited to <30 mA; in case of a shorted current limit circuit, current is limited to ~100 mA.
-
Field Device Cabling Distance:
- Maximum distance depends on compliance voltage (22.8 V dc), wire resistance, and voltage drop at the field device.
-
Visual Indicators: LEDs on the front of the module indicate Fieldbus Module status (power, communication, etc.).
-
Construction: Rugged extruded aluminum exterior for physical protection.
Power Requirements
-
Input Voltage Range (Redundant): 24 V dc +5%, -10%
-
Consumption: 7 W (maximum)
-
Heat Dissipation: 3 W (maximum)
Environmental Specifications
-
Operating Conditions:
-
Temperature: -20 to +70°C (-4 to +158°F)
-
Relative Humidity: 5 to 95% (non-condensing)
-
Altitude: -300 to +3,000 m (-1,000 to +10,000 ft)
-
Storage Conditions:
-
Temperature: -40 to +70°C (-40 to +158°F)
-
Relative Humidity: 5 to 95% (non-condensing)
-
Altitude: -300 to +12,000 m (-1,000 to +40,000 ft)
-
Contamination: Suitable for Class G3 (harsh) environments per ISA Standard S71.04, tested per EIA Standard 364-65, Class III
-
Vibration: 7.5 m/s² (0.75 g) from 5 to 500 Hz
Physical Specifications
-
Mounting:
- Mounts on a modular baseplate (DIN rail or 19-inch rack with mounting kit).
- Compatible with 100 Series conversion mounting structures.
-
Dimensions (FBM201):
-
Height: 102 mm (4 in); 114 mm (4.5 in) with mounting lugs
-
Width: 45 mm (1.75 in)
-
Depth: 104 mm (4.11 in)
-
Weight: Approximately 284 g (10 oz)
-
Termination Assembly (TA):
- Mounts on DIN rail (supports 32 mm and 35 mm styles).
-
Weight:
- Compression TA: ~181 g (0.40 lb)
- Ring Lug TA: ~249 g (0.55 lb)
-
Dimensions (TA): Refer to page 10 of the document for detailed TA dimensions.
Termination Assemblies and Cables
-
Termination Assemblies:
-
Compression Type (PA): RH916XG (supersedes P0916AA, P0916XG)
-
Ring Lug Type (PA): P0917JK (supersedes P0916AB)
-
Material: Polyamide (PA), rated from -20 to +70°C (-4 to +158°F)
-
Field Termination Connections:
-
Compression Type:
- Solid/Stranded: 0.2 to 4 mm² / 0.2 to 2.5 mm² (24 to 12 AWG)
- Stranded with Ferrules: 0.2 to 2.5 mm² (with or without plastic collar)
-
Ring Lug Type: #6 size connectors (0.375 in / 9.5 mm), 0.5 to 4 mm² (22 to 12 AWG)
-
Certification Types:
- Type 1: UL/UL-C listed for Class I, Groups A-D, Division 2, T4; DEMKO certified Ex nA IIC T4 for Zone 2.
- Type 2: UL/UL-C listed as associated apparatus for non-incendive field circuits in Class I, Groups A-D, Division 2, and Group IIC, Zone 2 (Class 2 limited energy).
-
Termination Cables:
-
Cable Lengths: Up to 30 m (98 ft)
-
Materials: Polyurethane or Low Smoke Zero Halogen (LSZH, -40 to +105°C)
-
Cable Type: Type 1
-
Connectors:
- FBM Baseplate End: 37-pin D-subminiature
- TA End: 25-pin D-subminiature
-
Part Numbers (examples):
- 0.5 m (1.6 ft): RH916DA (P/PVC), RH928AA (LSZH)
- 3.0 m (9.8 ft): RH916DC (P/PVC), RH928AD (LSZH)
- 30.0 m (98.4 ft): RH916DJ (P/PVC), RH928AK (LSZH)
- Full list in Table 2 (page 9 of document).
Regulatory Compliance
-
Electromagnetic Compatibility (EMC):
- Complies with European EMC Directive 2004/108/EC (prior to April 20, 2016) and 2014/30/EU (after April 20, 2016)
- Meets EN61326-1:2013 Class A Emissions and Industrial Immunity Levels
-
RoHS Compliance: Complies with European RoHS Directive 2011/65/EU
-
Product Safety:
-
UL/UL-C: Listed for Class I, Groups A-D, Division 2, T4; meets Class 2 requirements per NEC (NFPA No.70) and Canadian Electrical Code (CSA C22.1)
-
European Directives:
- Low Voltage Directive: 2006/95/EC (prior to April 20, 2016), 2014/35/EU (after April 20, 2016)
- ATEX Directive: 94/9/EC (prior to April 20, 2016), 2014/34/EU (after April 20, 2016)
- DEMKO certified Ex nA IIC T4 for Zone 2
-
Marine Certification:
- ABS Type Approved
- Bureau Veritas Marine certified for Environmental Category EC31
Functional Specifications
-
Process I/O Communications:
- Communicates with Fieldbus Communication Module (FCM) or Control Processor (FCP) via redundant 2 Mbps module Fieldbus.
- Supports communication over either path (A or B); switches to active path if one fails.
-
Calibration: No calibration required for the module or termination assembly.
-
Application Program:
- Executes an analog input application program with configurable options for integration time and Rate of Change Limits.
-
Fieldbus Compatibility: Interfaces electrical input signals to the redundant fieldbus, supporting HART signals.
-
- Manufacturer: Schneider Electric (Foxboro)
- Model Number: FBM201 (Part Number: RH914SQ, supersedes P0914SQ)
- Product Type: Analog Input Module
- Function: Provides eight analog input channels for 0 to 20 mA dc signals from analog sensors (e.g., 4 to 20 mA transmitters or self-powered 20 mA sources).
-
System Compatibility:
- Interfaces with the Foxboro Evo Process Automation System via a redundant 2 Mbps module Fieldbus.
- Electrically compatible with standard HART signals.
- Mounts on a modular baseplate accommodating up to four or eight FBMs, compatible with DIN rail or rack mounting.
Hardware Specifications
-
Input Channels: 8 isolated and independent channels
-
Input Range: 0 to 20 mA dc
-
Input Channel Impedance: 61.5 Ω nominal
-
Analog Accuracy (Includes Linearity): ±0.03% of span
-
Accuracy Temperature Coefficient: ±50 ppm/°C
-
Input Signal A/D Conversion: Each channel uses an independent Sigma-Delta converter, providing a new reading every 25 ms
-
Integration Period: Software configurable
-
Common Mode Rejection: >100 dB at 50 or 60 Hz
-
Normal Mode Rejection: >95 dB at 50 or 60 Hz
-
Input Channel Isolation:
- Each channel is galvanically isolated from other channels and ground.
- Withstands 600 V ac applied for one minute between any channel and ground or between channels (not intended for permanent connection to such voltages).
-
Loop Power Supply Protection:
- Each channel is galvanically isolated, current limited, and voltage regulated.
- Analog inputs limited to <30 mA; in case of a shorted current limit circuit, current is limited to ~100 mA.
-
Field Device Cabling Distance:
- Maximum distance depends on compliance voltage (22.8 V dc), wire resistance, and voltage drop at the field device.
-
Visual Indicators: LEDs on the front of the module indicate Fieldbus Module status (power, communication, etc.).
-
Construction: Rugged extruded aluminum exterior for physical protection.
Power Requirements
-
Input Voltage Range (Redundant): 24 V dc +5%, -10%
-
Consumption: 7 W (maximum)
-
Heat Dissipation: 3 W (maximum)
Environmental Specifications
-
Operating Conditions:
-
Temperature: -20 to +70°C (-4 to +158°F)
-
Relative Humidity: 5 to 95% (non-condensing)
-
Altitude: -300 to +3,000 m (-1,000 to +10,000 ft)
-
Storage Conditions:
-
Temperature: -40 to +70°C (-40 to +158°F)
-
Relative Humidity: 5 to 95% (non-condensing)
-
Altitude: -300 to +12,000 m (-1,000 to +40,000 ft)
-
Contamination: Suitable for Class G3 (harsh) environments per ISA Standard S71.04, tested per EIA Standard 364-65, Class III
-
Vibration: 7.5 m/s² (0.75 g) from 5 to 500 Hz
Physical Specifications
-
Mounting:
- Mounts on a modular baseplate (DIN rail or 19-inch rack with mounting kit).
- Compatible with 100 Series conversion mounting structures.
-
Dimensions (FBM201):
-
Height: 102 mm (4 in); 114 mm (4.5 in) with mounting lugs
-
Width: 45 mm (1.75 in)
-
Depth: 104 mm (4.11 in)
-
Weight: Approximately 284 g (10 oz)
-
Termination Assembly (TA):
- Mounts on DIN rail (supports 32 mm and 35 mm styles).
-
Weight:
- Compression TA: ~181 g (0.40 lb)
- Ring Lug TA: ~249 g (0.55 lb)
-
Dimensions (TA): Refer to page 10 of the document for detailed TA dimensions.
Termination Assemblies and Cables
-
Termination Assemblies:
-
Compression Type (PA): RH916XG (supersedes P0916AA, P0916XG)
-
Ring Lug Type (PA): P0917JK (supersedes P0916AB)
-
Material: Polyamide (PA), rated from -20 to +70°C (-4 to +158°F)
-
Field Termination Connections:
-
Compression Type:
- Solid/Stranded: 0.2 to 4 mm² / 0.2 to 2.5 mm² (24 to 12 AWG)
- Stranded with Ferrules: 0.2 to 2.5 mm² (with or without plastic collar)
-
Ring Lug Type: #6 size connectors (0.375 in / 9.5 mm), 0.5 to 4 mm² (22 to 12 AWG)
-
Certification Types:
- Type 1: UL/UL-C listed for Class I, Groups A-D, Division 2, T4; DEMKO certified Ex nA IIC T4 for Zone 2.
- Type 2: UL/UL-C listed as associated apparatus for non-incendive field circuits in Class I, Groups A-D, Division 2, and Group IIC, Zone 2 (Class 2 limited energy).
-
Termination Cables:
-
Cable Lengths: Up to 30 m (98 ft)
-
Materials: Polyurethane or Low Smoke Zero Halogen (LSZH, -40 to +105°C)
-
Cable Type: Type 1
-
Connectors:
- FBM Baseplate End: 37-pin D-subminiature
- TA End: 25-pin D-subminiature
-
Part Numbers (examples):
- 0.5 m (1.6 ft): RH916DA (P/PVC), RH928AA (LSZH)
- 3.0 m (9.8 ft): RH916DC (P/PVC), RH928AD (LSZH)
- 30.0 m (98.4 ft): RH916DJ (P/PVC), RH928AK (LSZH)
- Full list in Table 2 (page 9 of document).
Regulatory Compliance
-
Electromagnetic Compatibility (EMC):
- Complies with European EMC Directive 2004/108/EC (prior to April 20, 2016) and 2014/30/EU (after April 20, 2016)
- Meets EN61326-1:2013 Class A Emissions and Industrial Immunity Levels
-
RoHS Compliance: Complies with European RoHS Directive 2011/65/EU
-
Product Safety:
-
UL/UL-C: Listed for Class I, Groups A-D, Division 2, T4; meets Class 2 requirements per NEC (NFPA No.70) and Canadian Electrical Code (CSA C22.1)
-
European Directives:
- Low Voltage Directive: 2006/95/EC (prior to April 20, 2016), 2014/35/EU (after April 20, 2016)
- ATEX Directive: 94/9/EC (prior to April 20, 2016), 2014/34/EU (after April 20, 2016)
- DEMKO certified Ex nA IIC T4 for Zone 2
-
Marine Certification:
- ABS Type Approved
- Bureau Veritas Marine certified for Environmental Category EC31
Functional Specifications
-
Process I/O Communications:
- Communicates with Fieldbus Communication Module (FCM) or Control Processor (FCP) via redundant 2 Mbps module Fieldbus.
- Supports communication over either path (A or B); switches to active path if one fails.
-
Calibration: No calibration required for the module or termination assembly.
-
Application Program:
- Executes an analog input application program with configurable options for integration time and Rate of Change Limits.
-
Fieldbus Compatibility: Interfaces electrical input signals to the redundant fieldbus, supporting HART signals.
-
- Each channel is galvanically isolated from other channels and ground.
- Withstands 600 V ac applied for one minute between any channel and ground or between channels (not intended for permanent connection to such voltages).
- Each channel is galvanically isolated, current limited, and voltage regulated.
- Analog inputs limited to <30 mA; in case of a shorted current limit circuit, current is limited to ~100 mA.
- Maximum distance depends on compliance voltage (22.8 V dc), wire resistance, and voltage drop at the field device.
- Input Voltage Range (Redundant): 24 V dc +5%, -10%
- Consumption: 7 W (maximum)
- Heat Dissipation: 3 W (maximum)
Environmental Specifications
-
Operating Conditions:
-
Temperature: -20 to +70°C (-4 to +158°F)
-
Relative Humidity: 5 to 95% (non-condensing)
-
Altitude: -300 to +3,000 m (-1,000 to +10,000 ft)
-
Storage Conditions:
-
Temperature: -40 to +70°C (-40 to +158°F)
-
Relative Humidity: 5 to 95% (non-condensing)
-
Altitude: -300 to +12,000 m (-1,000 to +40,000 ft)
-
Contamination: Suitable for Class G3 (harsh) environments per ISA Standard S71.04, tested per EIA Standard 364-65, Class III
-
Vibration: 7.5 m/s² (0.75 g) from 5 to 500 Hz
Physical Specifications
-
Mounting:
- Mounts on a modular baseplate (DIN rail or 19-inch rack with mounting kit).
- Compatible with 100 Series conversion mounting structures.
-
Dimensions (FBM201):
-
Height: 102 mm (4 in); 114 mm (4.5 in) with mounting lugs
-
Width: 45 mm (1.75 in)
-
Depth: 104 mm (4.11 in)
-
Weight: Approximately 284 g (10 oz)
-
Termination Assembly (TA):
- Mounts on DIN rail (supports 32 mm and 35 mm styles).
-
Weight:
- Compression TA: ~181 g (0.40 lb)
- Ring Lug TA: ~249 g (0.55 lb)
-
Dimensions (TA): Refer to page 10 of the document for detailed TA dimensions.
Termination Assemblies and Cables
-
Termination Assemblies:
-
Compression Type (PA): RH916XG (supersedes P0916AA, P0916XG)
-
Ring Lug Type (PA): P0917JK (supersedes P0916AB)
-
Material: Polyamide (PA), rated from -20 to +70°C (-4 to +158°F)
-
Field Termination Connections:
-
Compression Type:
- Solid/Stranded: 0.2 to 4 mm² / 0.2 to 2.5 mm² (24 to 12 AWG)
- Stranded with Ferrules: 0.2 to 2.5 mm² (with or without plastic collar)
-
Ring Lug Type: #6 size connectors (0.375 in / 9.5 mm), 0.5 to 4 mm² (22 to 12 AWG)
-
Certification Types:
- Type 1: UL/UL-C listed for Class I, Groups A-D, Division 2, T4; DEMKO certified Ex nA IIC T4 for Zone 2.
- Type 2: UL/UL-C listed as associated apparatus for non-incendive field circuits in Class I, Groups A-D, Division 2, and Group IIC, Zone 2 (Class 2 limited energy).
-
Termination Cables:
-
Cable Lengths: Up to 30 m (98 ft)
-
Materials: Polyurethane or Low Smoke Zero Halogen (LSZH, -40 to +105°C)
-
Cable Type: Type 1
-
Connectors:
- FBM Baseplate End: 37-pin D-subminiature
- TA End: 25-pin D-subminiature
-
Part Numbers (examples):
- 0.5 m (1.6 ft): RH916DA (P/PVC), RH928AA (LSZH)
- 3.0 m (9.8 ft): RH916DC (P/PVC), RH928AD (LSZH)
- 30.0 m (98.4 ft): RH916DJ (P/PVC), RH928AK (LSZH)
- Full list in Table 2 (page 9 of document).
Regulatory Compliance
-
Electromagnetic Compatibility (EMC):
- Complies with European EMC Directive 2004/108/EC (prior to April 20, 2016) and 2014/30/EU (after April 20, 2016)
- Meets EN61326-1:2013 Class A Emissions and Industrial Immunity Levels
-
RoHS Compliance: Complies with European RoHS Directive 2011/65/EU
-
Product Safety:
-
UL/UL-C: Listed for Class I, Groups A-D, Division 2, T4; meets Class 2 requirements per NEC (NFPA No.70) and Canadian Electrical Code (CSA C22.1)
-
European Directives:
- Low Voltage Directive: 2006/95/EC (prior to April 20, 2016), 2014/35/EU (after April 20, 2016)
- ATEX Directive: 94/9/EC (prior to April 20, 2016), 2014/34/EU (after April 20, 2016)
- DEMKO certified Ex nA IIC T4 for Zone 2
-
Marine Certification:
- ABS Type Approved
- Bureau Veritas Marine certified for Environmental Category EC31
Functional Specifications
-
Process I/O Communications:
- Communicates with Fieldbus Communication Module (FCM) or Control Processor (FCP) via redundant 2 Mbps module Fieldbus.
- Supports communication over either path (A or B); switches to active path if one fails.
-
Calibration: No calibration required for the module or termination assembly.
-
Application Program:
- Executes an analog input application program with configurable options for integration time and Rate of Change Limits.
-
Fieldbus Compatibility: Interfaces electrical input signals to the redundant fieldbus, supporting HART signals.
-
- Temperature: -20 to +70°C (-4 to +158°F)
- Relative Humidity: 5 to 95% (non-condensing)
- Altitude: -300 to +3,000 m (-1,000 to +10,000 ft)
- Temperature: -40 to +70°C (-40 to +158°F)
- Relative Humidity: 5 to 95% (non-condensing)
- Altitude: -300 to +12,000 m (-1,000 to +40,000 ft)
-
Mounting:
- Mounts on a modular baseplate (DIN rail or 19-inch rack with mounting kit).
- Compatible with 100 Series conversion mounting structures.
-
Dimensions (FBM201):
- Height: 102 mm (4 in); 114 mm (4.5 in) with mounting lugs
- Width: 45 mm (1.75 in)
- Depth: 104 mm (4.11 in)
- Weight: Approximately 284 g (10 oz)
-
Termination Assembly (TA):
- Mounts on DIN rail (supports 32 mm and 35 mm styles).
-
Weight:
- Compression TA: ~181 g (0.40 lb)
- Ring Lug TA: ~249 g (0.55 lb)
- Dimensions (TA): Refer to page 10 of the document for detailed TA dimensions.
Termination Assemblies and Cables
-
Termination Assemblies:
-
Compression Type (PA): RH916XG (supersedes P0916AA, P0916XG)
-
Ring Lug Type (PA): P0917JK (supersedes P0916AB)
-
Material: Polyamide (PA), rated from -20 to +70°C (-4 to +158°F)
-
Field Termination Connections:
-
Compression Type:
- Solid/Stranded: 0.2 to 4 mm² / 0.2 to 2.5 mm² (24 to 12 AWG)
- Stranded with Ferrules: 0.2 to 2.5 mm² (with or without plastic collar)
-
Ring Lug Type: #6 size connectors (0.375 in / 9.5 mm), 0.5 to 4 mm² (22 to 12 AWG)
-
Certification Types:
- Type 1: UL/UL-C listed for Class I, Groups A-D, Division 2, T4; DEMKO certified Ex nA IIC T4 for Zone 2.
- Type 2: UL/UL-C listed as associated apparatus for non-incendive field circuits in Class I, Groups A-D, Division 2, and Group IIC, Zone 2 (Class 2 limited energy).
-
Termination Cables:
-
Cable Lengths: Up to 30 m (98 ft)
-
Materials: Polyurethane or Low Smoke Zero Halogen (LSZH, -40 to +105°C)
-
Cable Type: Type 1
-
Connectors:
- FBM Baseplate End: 37-pin D-subminiature
- TA End: 25-pin D-subminiature
-
Part Numbers (examples):
- 0.5 m (1.6 ft): RH916DA (P/PVC), RH928AA (LSZH)
- 3.0 m (9.8 ft): RH916DC (P/PVC), RH928AD (LSZH)
- 30.0 m (98.4 ft): RH916DJ (P/PVC), RH928AK (LSZH)
- Full list in Table 2 (page 9 of document).
Regulatory Compliance
-
Electromagnetic Compatibility (EMC):
- Complies with European EMC Directive 2004/108/EC (prior to April 20, 2016) and 2014/30/EU (after April 20, 2016)
- Meets EN61326-1:2013 Class A Emissions and Industrial Immunity Levels
-
RoHS Compliance: Complies with European RoHS Directive 2011/65/EU
-
Product Safety:
-
UL/UL-C: Listed for Class I, Groups A-D, Division 2, T4; meets Class 2 requirements per NEC (NFPA No.70) and Canadian Electrical Code (CSA C22.1)
-
European Directives:
- Low Voltage Directive: 2006/95/EC (prior to April 20, 2016), 2014/35/EU (after April 20, 2016)
- ATEX Directive: 94/9/EC (prior to April 20, 2016), 2014/34/EU (after April 20, 2016)
- DEMKO certified Ex nA IIC T4 for Zone 2
-
Marine Certification:
- ABS Type Approved
- Bureau Veritas Marine certified for Environmental Category EC31
Functional Specifications
-
Process I/O Communications:
- Communicates with Fieldbus Communication Module (FCM) or Control Processor (FCP) via redundant 2 Mbps module Fieldbus.
- Supports communication over either path (A or B); switches to active path if one fails.
-
Calibration: No calibration required for the module or termination assembly.
-
Application Program:
- Executes an analog input application program with configurable options for integration time and Rate of Change Limits.
-
Fieldbus Compatibility: Interfaces electrical input signals to the redundant fieldbus, supporting HART signals.
-
- Compression Type (PA): RH916XG (supersedes P0916AA, P0916XG)
- Ring Lug Type (PA): P0917JK (supersedes P0916AB)
- Material: Polyamide (PA), rated from -20 to +70°C (-4 to +158°F)
-
Field Termination Connections:
-
Compression Type:
- Solid/Stranded: 0.2 to 4 mm² / 0.2 to 2.5 mm² (24 to 12 AWG)
- Stranded with Ferrules: 0.2 to 2.5 mm² (with or without plastic collar)
- Ring Lug Type: #6 size connectors (0.375 in / 9.5 mm), 0.5 to 4 mm² (22 to 12 AWG)
-
Compression Type:
-
Certification Types:
- Type 1: UL/UL-C listed for Class I, Groups A-D, Division 2, T4; DEMKO certified Ex nA IIC T4 for Zone 2.
- Type 2: UL/UL-C listed as associated apparatus for non-incendive field circuits in Class I, Groups A-D, Division 2, and Group IIC, Zone 2 (Class 2 limited energy).
- Cable Lengths: Up to 30 m (98 ft)
- Materials: Polyurethane or Low Smoke Zero Halogen (LSZH, -40 to +105°C)
- Cable Type: Type 1
-
Connectors:
- FBM Baseplate End: 37-pin D-subminiature
- TA End: 25-pin D-subminiature
-
Part Numbers (examples):
- 0.5 m (1.6 ft): RH916DA (P/PVC), RH928AA (LSZH)
- 3.0 m (9.8 ft): RH916DC (P/PVC), RH928AD (LSZH)
- 30.0 m (98.4 ft): RH916DJ (P/PVC), RH928AK (LSZH)
- Full list in Table 2 (page 9 of document).
-
Electromagnetic Compatibility (EMC):
- Complies with European EMC Directive 2004/108/EC (prior to April 20, 2016) and 2014/30/EU (after April 20, 2016)
- Meets EN61326-1:2013 Class A Emissions and Industrial Immunity Levels
- RoHS Compliance: Complies with European RoHS Directive 2011/65/EU
-
Product Safety:
- UL/UL-C: Listed for Class I, Groups A-D, Division 2, T4; meets Class 2 requirements per NEC (NFPA No.70) and Canadian Electrical Code (CSA C22.1)
-
European Directives:
- Low Voltage Directive: 2006/95/EC (prior to April 20, 2016), 2014/35/EU (after April 20, 2016)
- ATEX Directive: 94/9/EC (prior to April 20, 2016), 2014/34/EU (after April 20, 2016)
- DEMKO certified Ex nA IIC T4 for Zone 2
-
Marine Certification:
- ABS Type Approved
- Bureau Veritas Marine certified for Environmental Category EC31
Functional Specifications
-
Process I/O Communications:
- Communicates with Fieldbus Communication Module (FCM) or Control Processor (FCP) via redundant 2 Mbps module Fieldbus.
- Supports communication over either path (A or B); switches to active path if one fails.
-
Calibration: No calibration required for the module or termination assembly.
-
Application Program:
- Executes an analog input application program with configurable options for integration time and Rate of Change Limits.
-
Fieldbus Compatibility: Interfaces electrical input signals to the redundant fieldbus, supporting HART signals.
-
- Communicates with Fieldbus Communication Module (FCM) or Control Processor (FCP) via redundant 2 Mbps module Fieldbus.
- Supports communication over either path (A or B); switches to active path if one fails.
- Executes an analog input application program with configurable options for integration time and Rate of Change Limits.