Product Description
Foxboro 13AMS2 Differential Pressure Transmitter
Product Overview
- The Foxboro 13AMS2 is a Differential Pressure Transmitter designed by Foxboro (now part of Schneider Electric) for use in industrial process control systems. This transmitter measures the difference in pressure between two points in a process system and converts it into a standardized signal (typically 4_20 mA) for monitoring and control. It is widely used in industries such as oil and gas, chemical processing, power generation, and water treatment for applications like flow measurement, level measurement, and pressure monitoring in liquids, gases, or vapors. The 13AMS2 is part of the Foxboro 13A series, known for its rugged design and reliability in harsh environments.
Technical Specifications
- The 13AMS2 has the following specifications
| Specification | Details |
|---|---|
| Model/Part Number | 13AMS2 |
| Manufacturer | Foxboro (Schneider Electric) |
| Description | Differential Pressure Transmitter |
| Series | Foxboro 13A Series |
| Function | Measures differential pressure and converts to 4_20 mA output signal |
| Pressure Range | Adjustable spans, typically 0_50 to 0_1000 inH2O (0_12.4 to 0_248 kPa) |
| Output Signal | 4_20 mA DC (analog, 2-wire) |
| Accuracy | ±0.5% of span (typical) |
| Process Connection | 1/4 NPT or 1/2 NPT (standard, with optional adapters) |
| Wetted Materials | 316 stainless steel (diaphragm and body), optional Hastelloy C or Monel |
| Body Material | 316 stainless steel or carbon steel (depending on configuration) |
| Maximum Working Pressure | Up to 3000 psig (20.7 MPa), depending on model configuration |
| Power Supply | 12_42 VDC (loop-powered) |
| Electrical Connection | 1/2 NPT conduit or terminal block |
| Environmental Specifications | Operating Temperature: -40°C to +85°C (-40°F to +185°F) Storage Temperature: -40°C to +93°C (-40°F to +200°F) Relative Humidity: 0% to 100% (weatherproof) Vibration: Resistant per ISA standards Enclosure: NEMA 4X, IP66 (weatherproof and corrosion-resistant) |
| Dimensions | Approx. 300 mm (H) x 150 mm (W) x 150 mm (D) (varies by configuration) |
| Weight | Approx. 4_6 kg (depending on materials and options) |
| Mounting | Pipe mount (2-inch pipe), wall mount, or manifold mount |
| Certifications | FM, CSA, ATEX (optional for hazardous areas), CE compliant |
_