Product Description
Emerson VE4005S2B3 DeltaV M-series Discrete Output Module
- Manufacturer: Emerson
- Model/Part Number: VE4005S2B3 (Alternate: KJ3223X1-BA1, 12P2871X)
- Description: M-series Discrete Output Module, 16-Channel, 4-20 mA, HART, with 16-Pin Mass Termination Block
Overview
- The Emerson VE4005S2B3 is an M-series Discrete Output Module designed for the DeltaV Distributed Control System. It provides 16-channel, 4-20 mA outputs with HART communication, paired with a 16-pin mass termination block for efficient wiring. The module controls field devices such as valves and actuators in industrial automation applications, including oil and gas, chemical, and power generation, ensuring reliable process control.
Technical Specifications
Specification | Details |
---|---|
Model | VE4005S2B3 (KJ3223X1-BA1) |
Series | DeltaV M-series |
Type | Discrete Output Module, 16-Channel, 4-20 mA, HART, with 16-Pin Mass Termination Block |
Channels | 16 analog output channels |
Output Signal | 4-20 mA, HART protocol |
LocalBus Power | 12 VDC at 300 mA |
Field Circuit Power | 24 VDC at 600 mA |
Weight | 0.4 kg |
Operating Temperature | -40°C to +70°C |
Storage Temperature | -40°C to +85°C |
Relative Humidity | 5% to 95%, non-condensing |
Protection Rating | IP20 |
Airborne Contaminants | ISA-S71.04-1985 Class G3, conformal coating |
Mounting | T-type DIN rail, on I/O carrier |
Certifications | CE, CSA, FM, ATEX, IECEx, Marine Certifications (ABS, DNV) |
System Compatibility | DeltaV v10.3 or later |
Additional Information
- Functionality: The VE4005S2B3 delivers 16 4-20 mA analog outputs with HART communication for precise control and diagnostics of field devices. The 16-pin mass termination block simplifies wiring, reducing installation time. The module supports hot-swappable installation, enabling maintenance without system downtime, and includes diagnostics for detecting faults like short circuits.
- Environmental Durability: Designed for harsh industrial environments, the module features conformal coating to protect against airborne contaminants and operates reliably in extreme temperatures, shock, and vibration conditions. It is suitable for hazardous area installations, including Zone 2.