Product Description
Emerson VE4005S2B1 DeltaV M-series Analog Output Module
- Manufacturer: Emerson
- Model/Part Number: VE4005S2B1 (Alternate: KJ3221X1-BA1, 12P2531X)
- Description: M-series Analog Output Module, 8-Channel, 4-20 mA, HART, with Standard I/O Termination Block
Overview
- The Emerson VE4005S2B1 is an M-series Analog Output Module designed for the DeltaV Distributed Control System. It provides 8-channel, 4-20 mA outputs with HART communication and includes a standard I/O termination block for secure connections. The module controls field devices such as valves and actuators in industrial automation applications, including oil and gas, chemical, and power generation, ensuring precise process control.
Technical Specifications
Specification | Details |
---|---|
Model | VE4005S2B1 (KJ3221X1-BA1) |
Series | DeltaV M-series |
Type | Analog Output Module, 8-Channel, 4-20 mA, HART, with Standard I/O Termination Block |
Channels | 8 analog output channels |
Output Signal | 4-20 mA, HART protocol |
LocalBus Power | 12 VDC at 300 mA |
Field Circuit Power | 24 VDC at 600 mA |
Weight | 0.4 kg |
Operating Temperature | -40°C to +70°C |
Storage Temperature | -40°C to +85°C |
Relative Humidity | 5% to 95%, non-condensing |
Protection Rating | IP20 |
Airborne Contaminants | ISA-S71.04-1985 Class G3, conformal coating |
Mounting | T-type DIN rail, on I/O carrier |
Certifications | CE, CSA, FM, ATEX, IECEx, Marine Certifications (ABS, DNV) |
System Compatibility | DeltaV v10.3 or later |
Additional Information
- Functionality: The VE4005S2B1 delivers eight 4-20 mA analog outputs with HART communication for precise control and diagnostics of field devices. The standard I/O termination block ensures reliable and straightforward wiring. The module supports hot-swappable installation, enabling maintenance without system downtime, and includes diagnostics for detecting faults like short circuits.
- Environmental Durability: Designed for harsh industrial environments, the module features conformal coating to protect against airborne contaminants and operates reliably in extreme temperatures, shock, and vibration conditions. It is suitable for hazardous area installations, including Zone 2