Product Description
| Model Description | |
|---|---|
| Field | Details |
| Model | VE4002S2T2B8 |
| Description | Discrete Output Plus Card, 32 Channels, 24V DC, High-Side. Includes a 40-pin DO Mass Termination Block for Series 2 Plus (to be used with DeltaV Signal Conditioning Cards for PLC-5 DO, or P+F HiC IS barriers and terminal boards for DeltaV DCS). |
| Technical Specifications | |
|---|---|
| Parameter | Specification |
| Number of Channels | 32 |
| Isolation | Each channel is optically isolated from the system and factory tested to 1500 V DC. |
| Output Voltage Range | 24V DC ±10% |
| Output Rating | 100 mA per channel |
| Off-state Leakage | Max 0.1 mA |
| LocalBus Current (12V DC nominal) | Typical: 100 mA<br>Maximum: 150 mA |
| Field Circuit Power | 3.2 A @ 24V DC (+20%/-15%) per I/O interface |
| Return | Uses common return |
| Terminal Block | 32-screw termination block |
| Field Wiring | 2-wire—non-arcing<br>2-wire—nA (non-sparking) |
| Compatibility | |
|---|---|
| Component | Specification |
| I/O Card Keying | B4 |
| Conventional I/O Terminal Block | 32-Channel DO Terminal Block for Series 2 Plus |
| Mass Termination Block | 40-pin DO Mass Termination Block for Series 2 Plus |
| Certifications | |
|---|---|
| Certification Type | Details |
| FM (USA) | Class I, Division 2, Groups A, B, C, D, T4 |
| cFM (Canada) | Class I, Division 2, Groups A, B, C, D, T4 |
| ATEX | II 3G Ex nA IIC T4 Gc |
| IEC-Ex | Ex nA IIC T4 Gc |
| Zone 2 Ex nA Certified | Yes |
| Zone 2 Ex nL / Ex ic | No |
| Class I Division II Non-Incendive | No |
| Additional Information | |
|---|---|
| Field | Details |
| System Compatibility | M-series Traditional I/O cards are not physically compatible with S-series controller carriers. Requires DeltaV v13.3.1 or higher software. |
| Ordering Information | VE4002S2T2B8 includes 40-pin DO Mass Termination Block for Series 2 Plus (to be used with DeltaV Signal Conditioning Cards for PLC-5 DO, or P+F HiC IS barriers and terminal boards for DeltaV DCS). |
| Termination Fault Detection | Supported when used with the redundant 40-pin Mass DO Terminal Block combined with the M-series Mass Connection Solutions or P+F HiC IS barriers and termination boards for DeltaV DCS. |
| Installation Instructions | Refer to:<br>• Class 1 Division 2 Installation Instructions DeltaV M-Series 12P1293<br>• Zone 2 Installation Instructions DeltaV M-Series 12P2046 |
| Reference Documents | |
|---|---|
| Document | Description |
| PDS M-series Mass Connection Solution | For further details on the Mass Connection Boards |
| Installation Standards | Ensure compliance with standards and certifications detailed in installation documentation. |