Product Description
📘
Product Overview
|
Field |
Details |
|---|---|
|
Manufacturer |
Emerson |
|
Model/Part Number |
SE4058 |
|
Product Type |
DeltaV SIS S-series Adapter |
|
Function |
Connects M-series horizontal carriers to S-series controllers to allow SIS logic solvers on the same node |
|
System Compatibility |
DeltaV v11.3.1+ (for CHARM I/O), v14.3+ (for controller compatibility); Not for M-series I/O on S-series controllers |
⚙️
Hardware & System Integration
|
Parameter |
Specification |
|---|---|
|
Mounting |
Snap-on to T-type DIN rail (tool-less install with blade screwdriver release) |
|
I/O Carrier Capacity |
Up to 8 I/O modules per carrier; up to 8 I/O carriers (64 simplex / 32 redundant cards) |
|
Bus Extenders Support |
Yes; for extended I/O expansion |
|
Power Distribution |
Redundant 24VDC bussed field power |
|
Power Plugs |
Fused Power Buss Plugs (5A), or Terminal Plugs (12A) |
|
Primary Power Routing |
Odd-numbered slots = primary power, even = redundant via plugs |
|
Backplane Current |
15 A (I/O carrier relevant) |
|
Power Supply |
Requires 24V DC bulk power |
🌐
Modular & Shielding Design
|
Feature |
Details |
|---|---|
|
Modular Design |
Integrates into S-series horizontal carriers; supports online expansion |
|
Bus Shield Grounding |
Integrated ground bar for field noise isolation |
|
CHARM Support |
Not directly applicable – for logic solver connectivity via carriers |
|
Connection Method |
Bus-integrated; likely plug-in connection to S-series backplane |
🌡️
Environmental Specifications
|
Parameter |
Specification |
|---|---|
|
Operating Temp |
-40°C to +70°C |
|
Storage Temp |
-40°C to +85°C |
|
Relative Humidity |
5 to 95%, non-condensing |
|
Protection Rating |
IP20 |
|
Airborne Contaminants |
ISA-S71.04-1985 Class G3 (harsh), with conformal coating |
|
Shock |
10 g, ½-sine wave, 11 ms |
|
Vibration |
1 mm (2–13.2 Hz), 0.7 g (13.2–150 Hz) |
✅
Certifications
|
Standard |
Details |
|---|---|
|
CE |
EN 61326-1 (EMC) |
|
FM (USA) |
FM 3600, FM 3611; Class I, Div 2, Groups A–D, T4 |
|
cFM (Canada) |
CSA-C22.2 No. 213, No. 1010-1; Class I, Div 2, Groups A–D, T4 |
|
ATEX |
EN 60079-0, EN 60079-7; II 3G Ex ec IIC T4 Gc |
|
IEC-Ex |
IEC 60079-0, IEC 60079-7; II 3G Ex ec IIC T4 Gc |
|
Marine |
IACS E10, ABS Design Assessment, DNV Marine Certificate |
📋
Installation Notes
|
Document Reference |
Purpose |
|---|---|
|
12P5402 – Class 1 Division 2 Install Instructions |
US hazardous area wiring |
|
12P5404 – Zone 2 Installation Instructions |
International hazardous area wiring |
🛒
Ordering Summary
|
Part Number |
Description |
|---|---|
|
SE4058 |
S-series Adapter for connecting SIS logic solvers via M-series carriers to S-series controller nodes |