Product Description
📘 Product Overview
Field | Details |
---|---|
Manufacturer | Emerson |
Model Number | SE4002S1T2B6 |
Product Type | S-series Discrete Output Card, 32-channel, 24V DC, High-Side with 40-pin Mass I/O Terminal Block |
Function | Provides 32 discrete output channels for 24V DC high-side switching |
System Compatibility | DeltaV S-series controllers (SX, SQ), DeltaV v11.3.1 and higher |
Included Components | Discrete Output Card (32-channel, 24V DC, High-Side), 40-pin Mass I/O Terminal Block |
⚙️ Hardware Specifications
Feature | Specification |
---|---|
Number of Channels | 32 |
Output Range | 24V DC ±10% |
Output Rating | 100 mA per channel |
Off-State Leakage | 0.1 mA maximum |
LocalBus Current | 100 mA typical, 150 mA maximum (12V DC nominal) |
Field Circuit Power | 3.2 A maximum at 24V DC (+20%/-15%) |
Isolation | Each channel optically isolated from the system, factory tested to 1500V DC |
Termination Fault Detection | Available when used with S-series Mass Connection Solutions or P+F HIC IS barriers and boards |
🔌 Communication and Configuration
Feature | Specification |
---|---|
Configurable Channel Types | - Discrete Output: Output stays in last state submitted by control logic - Momentary Output: Output active for a pre-configured time period - Continuous Pulse Output: Active as a percentage of a pre-configured base time period (100 ms to 100 s), resolution 5 ms |
Configuration | Auto-sensed by DeltaV controller; configured via DeltaV Explorer |
Communication | Interfaces with DeltaV DCS for control and diagnostics |
🔁 Redundancy Features
Feature | Details |
---|---|
Redundancy Option | Available as redundant pair (model SE4032S1T2B8, includes 2 DO Plus Cards with 40-pin Mass Terminal Block) |
Redundancy Setup | Autosensed by DeltaV system; install on redundant 40-pin Mass Terminal Block |
Switchover Triggers | Hardware failure, communication failure, field wiring fault, manual switch via Diagnostics Explorer |
Switchover Time | Within two scans of the I/O bus; make-before-break contacts ensure process continuity |
Standby Operation | Standby card scanned by controller; health and status reported via Diagnostics Explorer |
Notification | Hardware alerts report integrity errors; switchover events logged in Event Chronicle |
Replacement | Auto-commissioned standby card; replaceable under power in safe areas, follow hazardous area procedures |
🌡️ Environmental Specifications
Parameter | Specification |
---|---|
Operating Temperature | -40 to 70 °C (-40 to 158 °F) |
Storage Temperature | -40 to 85 °C (-40 to 185 °F) |
Relative Humidity | 5 to 95%, non-condensing |
Airborne Contaminants | ISA-S71.04-1985 Class G3, conformal coating |
Protection Rating | IP20 |
Shock | 10 g ½-sine wave for 11 ms |
Vibration | 1 mm peak-to-peak (2–13.2 Hz), 0.7 g (13.2–150 Hz) |
✅ Certifications
Standard | Details |
---|---|
CE | EMC - EN 61326-1 |
FM (USA) | Class I, Division 2, Groups A, B, C, D, T4 |
cFM (Canada) | Class I, Division 2, Groups A, B, C, D, T4 |
ATEX | II 3G Ex ec IIC T4 Gc, II 3G Ex nA nC IIC T4 Gc |
IEC-Ex | II 3G Ex ec IIC T4 Gc, II 3G Ex nA nC IIC T4 Gc |
Marine | IACS E10, ABS Certificate of Design Assessment, DNV Marine Certificate |
Installation Instructions | Class I Division 2: 12P5402; Zone 2: 12P5404 |
🛠️ Installation and Configuration
Feature | Details |
---|---|
Installation | Plugs into any slot on 8-wide I/O carrier; snaps onto T-DIN rail |
Removal/Insertion | Cannot be removed/inserted with system power energized; field power must be removed; non-sparking field circuits must be de-energized |
Terminal Block Compatibility | Discrete 32-channel Terminal Block, 40-pin Mass Terminal Block (simplex), Redundant 40-pin Mass Terminal Block |
I/O Card Keying | B4 |
Maintenance | No user-serviceable parts; no calibration required |
📦 Ordering Information
Description | Model Number |
---|---|
Discrete Output, 32-channel, 24V DC, High-Side | SE4002S1T2B5 (with Discrete 32-channel Terminal Block) |
Discrete Output, 32-channel, 24V DC, High-Side | SE4002S1T2B6 (with 40-pin Mass I/O Terminal Block) |
Discrete Output, 32-channel, 24V DC, High-Side | SE4002S1T2B6 (with 40-pin Mass I/O Terminal Block, including 4 x 8-channel DO Mass Connection Boards) |
Redundant Discrete Output, 32-channel, 24V DC, High-Side | SE4032S1T2B8 (2 x DO Plus Cards with 40-pin Mass Terminal Block) |
Spare Fuse (250V 2A) | KJ4010X1-BC1 (Box of 20) |
📝 Additional Notes
- Mass Terminal Block: The 40-pin Mass Terminal Block supports S-series Mass Connection Solutions or third-party solutions (e.g., Pepperl+Fuchs HIC IS barriers).
- Wiring: Terminal block allows removal of I/O card without disconnecting field wiring.
- Redundancy: Redundant configuration (SE4032S1T2B8) uses two DO Plus Cards on a redundant 40-pin Mass Terminal Block; no special configuration needed.
- System Integration: Supports control module-level time stamping; integrates with DeltaV DCS for alarms and events.
- Hazardous Area Operation: Follow installation instructions for Class I Division 2 (12P5402) and Zone 2 (12P5404).