Product Description
📘 Product Overview
Field | Details |
---|---|
Manufacturer | SolaHD (Emerson) |
Model Number | SDN 5-24-100C (optional "X" suffix for conformal coated version) |
Product Type | Single Phase DIN Rail Power Supply |
Applications | Industrial Automation, Process Control, Material Handling, Hazardous Locations, Marine Applications |
Features | PowerBoost™, 3 LED diagnostics, DC OK relay, universal AC/DC input, parallel operation, supports SDN-C Redundancy Modules, 5-year limited warranty |
Corrosion Resistance | Conformal coated versions ("X" suffix) meet G3 Harsh Rating per ISA 71.04 Group A |
⚡ Input Specifications
Parameter | Specification |
---|---|
Nominal AC Voltage (Range) | 100-240 Vac (85-264 Vac) |
Nominal DC Voltage (Range) | 100-340 Vdc (90-375 Vdc) |
Frequency | 43-67 Hz |
Nominal Current | 1.65-0.55 A (at low AC input, worst-case efficiency) |
Inrush Current | <3.7 A at 120 Vac, <7.4 A at 230 Vac, measured at 25°C |
Efficiency (Losses) | >88% typical (14 W at full load, nominal AC input) |
Power Factor Correction | Active Power Factor Correction |
🔌 Output Specifications
Parameter | Specification |
---|---|
Nominal Voltage | 24 V (23.5-28.5 Vdc adjustable) |
Initial Voltage Setting | 24.5 V ± 1% |
Tolerance | <±2% overall (line, load, time, and temperature-related changes) |
Ripple | <100 mVpp |
PARD (Periodic and Random Deviation) | Not specified for this model (typically aligns with ripple) |
Nominal Current (Rated Power) | 5 A (120 W at +60°C) |
Parallel Operation | Single or parallel operation; requires SDN-C Redundancy Module for redundancy |
Turn On Time | <1 s after AC is applied at full load |
Holdup Time | 20 ms (full load, 100 Vac input at +25°C) |
Voltage Fall Time | <150 ms from 95% to 10% rated voltage |
Short Circuit Protection | Output goes to near zero, auto-recovery |
Peak Current | 1.5 × Nominal Current (>7.5 A) for >4 seconds, holding voltage >20 Vdc |
Current Limit | PowerBoost™ |
Back EMF Immunity | <35 V, no damage, auto-recovery |
Overvoltage Protection | >30.5 but <33 Vdc, auto-recovery |
Overtemperature Protection | LED alarm and output shutdown, auto-recovery |
🌡️ Environmental Specifications
Parameter | Specification |
---|---|
Operating Temperature | -40 to +70°C (contact tech support for operation at -40°C) |
Storage Temperature | -40 to +85°C |
Humidity | 95% non-condensing |
Vibration | DIN rail: IEC 60068-2-6; 10-500 Hz, 2 g, 10 sweeps/axis; Panel mount: 10-500 Hz, 1 g, 10 sweeps/axis |
Shock | IEC 60068-2-27; DIN rail: 15 g, 11 ms, 3 axes; Panel mount: 10 g, 11 ms, 3 axes |
Cooling | Convection |
✅ Certifications and Compliances
Standard | Details |
---|---|
UL Listed | UL 508, CSA C22.2 No. 107.1 (Ind. Control Equipment, E61379) |
UL Recognized | UL/CSA 60950-1, UL/CSA 62368-1 (ITE, E137632) |
Hazardous Locations | UL Recognized, Class I, Div 2; Class I, Zone 2; T4 (E234790); UL60079-0, CSA E60079-0, UL60079-15, CSA E60079-15; Class I, Zone 2, AEx ec nC IIC, Ex ec nC IIC |
ATEX | II 3 G, Ex ec nC IIC Gc (EN IEC 60079-0, 60079-7, 60079-15) |
IECEx | Ex ec nC IIC Gc (IEC 60079-0, 60079-7, 60079-15) |
CE | Low Voltage Directive, IEC/EN62368-1, IEC/EN60950-1 |
Marine Certifications | ABS, DNV-GL Type Approved |
Other | TR CU 012/2011 (Safety of Equipment for Explosive Atmospheres), RoHS Compliant |
🛠️ Installation and Mounting
Parameter | Details |
---|---|
Mounting | DIN Rail: Snap-on with tilt, push down, lock, and shake to ensure retention; Optional Panel Mount with SDN-PMBRK3 bracket (adds 2-4 mm depth) |
Panel Mount Bracket | SDN-PMBRK3 (compatible with SDN 5-24-100C) |
Multiple Output Connections | Dual output terminals for ease of wiring multiple devices |
Diagnostics | 3 LEDs (Input, Output, Alarm) with status conditions (Normal, AC Power Loss, AC Input Low, No DC, High Load, Overload, Hot, Too Hot) |
📏 Physical Specifications
Parameter | Specification |
---|---|
Dimensions (W x H x D) | 50 mm x 123 mm x 111 mm (1.97 in x 4.85 in x 4.36 in) |
Weight | 0.55 kg (1.2 lb) |
IP Rating | IP20 |