Product Description
General Information
|
Field |
Description |
|---|---|
|
Manufacturer |
Emerson |
|
Model/Part Number |
KJ4006X1-BS1 |
|
Description |
Redundant AI 8-Channel Terminal Block |
_
_
Power Specifications
|
Parameter |
Value |
|---|---|
|
Field Power |
30 VDC at 200 mA |
_
_
Environmental Specifications
|
Parameter |
Value |
|---|---|
|
Ambient Temperature |
-40°C to +70°C |
|
Shock |
10g ½ Sinewave for 11 ms |
|
Vibration |
1 mm Peak to Peak from 2_13.2 Hz; 0.7 g from 13.2_150 Hz |
|
Airborne Contaminants |
ISA-S71.04 _1985 Class G3 |
|
Relative Humidity |
5% to 95% Non-Condensing |
|
Terminal Block Key |
Set according to I/O card installed |
_
_
Important Notes
_
-
Hazardous Area Installation:
_
-
Refer to_Document 12P5404___DeltaV_ S-Series Digital Automation System Zone 2 Installation Instructions
-
Additional instructions in_DeltaV_ M-Series and CHARMs Hardware Installation_manual
-
Installation & Removal Guidelines:
_
-
Can be added or removed while system power is on, but_only if no I/O card is installed_and_no field wiring is connected
-
Rotary_keying system_ensures compatibility between terminal blocks and I/O cards
-
Maintenance:
_
-
No user-serviceable parts
-
Disassembly is not permitted
-
No calibration required