Product Description
Emerson KJ4006X1-BL1 DeltaV AI 8-Channel Terminal Block
- Manufacturer: Emerson
- Model/Part Number: KJ4006X1-BL1 (Alternate: 12P4730X)
- Description: DeltaV Analog Input 8-Channel Terminal Block, 2- or 4-Wire Configuration
Overview
- The Emerson KJ4006X1-BL1 is a DeltaV Analog Input Terminal Block designed for the DeltaV Distributed Control System. It supports 8 channels for analog input signals in 2- or 4-wire configurations, enabling connections to field devices such as transmitters and sensors. The terminal block is used in industrial automation applications, including oil and gas, chemical, and power generation, ensuring accurate data acquisition for process control.
Technical Specifications
Specification | Details |
---|---|
Model | KJ4006X1-BL1 (12P4730X) |
Series | DeltaV |
Type | Analog Input Terminal Block, 8-Channel, 2- or 4-Wire |
Channels | 8 analog input channels |
Supported Signals | 4-20 mA, compatible with 2- or 4-wire devices |
Field Circuit Rating | 30 VDC at 100 mA |
Operating Temperature | -40°C to +70°C |
Storage Temperature | -40°C to +85°C |
Relative Humidity | 5% to 95%, non-condensing |
Shock | 10 g half-sine wave for 11 ms |
Vibration | 1 mm peak-to-peak from 2 to 13.2 Hz, 0.7 g from 13.2 to 150 Hz |
Airborne Contaminants | ISA-S71.04-1985 Class G3, conformal coating |
Protection Rating | IP20 |
Mounting | T-type DIN rail, on I/O carrier |
Weight | Approximately 0.2 kg |
Certifications | CE, CSA, FM, ATEX, IECEx |
System Compatibility | DeltaV v10.3 or later |
Additional Information
- Functionality: The KJ4006X1-BL1 supports 8 analog input channels for 2- or 4-wire devices, typically handling 4-20 mA signals from field instruments like pressure or temperature transmitters. It ensures accurate data acquisition and is key-coded for compatibility with DeltaV analog input cards. The terminal block is not user-serviceable and requires no calibration.
- Environmental Durability: Designed for harsh industrial environments, the terminal block features conformal coating to protect against airborne contaminants and operates reliably in extreme temperatures, shock, and vibration conditions. It is suitable for use in hazardous areas with appropriate certifications.