Product Description
Model Description | |
---|---|
Field | Details |
Model | KJ4005X1-BC1 |
Description | Power Terminal Plug for 2-Wide and 8-Wide S-series Horizontal Carriers. |
Technical Specifications | |
---|---|
Parameter | Specification |
Power Terminal Plug Capacity | 12 Amps |
Compatibility | Compatible with 2-Wide Power/Controller Carriers and 8-Wide I/O Interface Carriers. Supports individual power connection for each I/O card, suitable for 24V DC or 120/230V AC. |
Additional Information | |
---|---|
Field | Details |
System Compatibility | Designed for S-series Horizontal Carriers. Used to bring dedicated power to each I/O card, as an alternative to Power Buss Plugs. Can be mixed with Power Buss Plugs on the same I/O Carrier. |
Ordering Information | Available as a single Power Terminal Plug (KJ4005X1-BC1) or as a package of 8 plugs (SE6197). |
Installation Instructions | Refer to:<br>• Class 1 Division 2 Installation Instructions DeltaV S-Series (12P5402)<br>• Zone 2 Installation Instructions DeltaV S-Series (12P5404) |
Certifications | |
---|---|
Certification Type | Details |
FM (USA) | Class I, Division 2, Groups A, B, C, D, T4 |
cFM (Canada) | Class I, Division 2, Groups A, B, C, D, T4 |
ATEX | II 3G Ex ec IIC T4 Gc |
IEC-Ex | II 3G Ex ec IIC T4 Gc |
Marine Certifications | ABS Certificate of Design Assessment<br>DNV Marine Certificate |
Environmental Specifications | |
---|---|
Parameter | Specification |
Operating Temperature | -40 to 70°C (-40 to 158°F) |
Storage Temperature | -40 to 85°C (-40 to 185°F) |
Relative Humidity | 5 to 95%, non-condensing |
Airborne Contaminants | ISA-S71.04-1985 Airborne Contaminants Class G3 Conformal coating |
Protection Rating | IP 20 |
Shock | 10 g ½-sine wave for 11 ms |
Vibration | 1 mm peak-to-peak from 5 to 13.2 Hz, 0.7 g from 13.2 to 150 Hz |