Product Description
General Information
Field |
Detail |
---|---|
Manufacturer |
Emerson |
Model/Part Number |
KJ3225X1-BK1 |
Description |
S-Series RTD / Resistance Input Card |
Power Specifications
Specification |
Detail |
---|---|
Local Bus Power |
12 VDC at 160 mA |
Environmental Specifications
Specification |
Detail |
---|---|
Ambient Temperature |
-40°C to +70°C |
Shock |
10g, ½ Sinewave for 11 milliseconds |
Vibration |
1mm Peak-to-Peak (2 to 13.2 Hz); 0.7g (13.2 to 150 Hz) |
Airborne Contaminants |
ISA-S71.04-1985 Class G3 |
Relative Humidity |
5% to 95% Non-Condensing |
Terminal Block Key Position |
C3 |
Special Instructions & Notes
-
Hazardous Area Installation:
Follow document 12P5404 “DeltaV™ S-Series Digital Automation System Zone 2 Installation Instructions”.
Additional installation guidance is in the “DeltaV™ S-Series and CHARMs Hardware Installation” manual.
-
Removal and Insertion:
-
Field power must be disconnected before removing or inserting the device.
-
The unit cannot be hot-swapped with system power energized.
-
For “nL” (energy-limited) installation, an I/O loop assessment is required.
-
Maintenance:
-
No user-serviceable parts inside.
-
Disassembly is not permitted.
-
Calibration is not required.