Product Description
Emerson KJ1501X1-BC2 DeltaV System Dual DC Power Supply
- Manufacturer: Emerson
- Model/Part Number: KJ1501X1-BC2 (Alternate: 12P2186X042, VE5009)
- Description: DeltaV System Dual DC Power Supply, 12/24 VDC Input, 12 VDC Output
Overview
- The Emerson KJ1501X1-BC2 is a DeltaV System Dual DC Power Supply designed for the DeltaV Distributed Control System (DCS). It provides reliable power to DeltaV controllers, I/O modules, and associated components, ensuring uninterrupted operation in industrial automation applications, such as oil and gas, chemical, power generation, and pharmaceuticals. The dual DC design enhances system reliability by offering redundant power sources.
Technical Specifications
Specification | Details |
---|---|
Model | KJ1501X1-BC2 (12P2186X042, VE5009) |
Series | DeltaV |
Type | System Dual DC Power Supply |
Input Rating | 12 VDC at 14.8 A or 24 VDC at 6.1 A |
Output Rating | 12 VDC at 10 A total (8 A for controller, 2 A for I/O) |
Max Output Power | 120 W |
Operating Temperature | -40°C to +70°C |
Storage Temperature | -40°C to +85°C |
Relative Humidity | 5% to 95%, non-condensing |
Protection Rating | IP20 |
Airborne Contaminants | ISA-S71.04-1985 Class G3, conformal coating |
Mounting | T-type DIN rail, on DeltaV controller carrier |
Weight | Approximately 0.9 kg |
Certifications | CE, CSA, FM, ATEX, IECEx (Zone 2) |
System Compatibility | DeltaV v10.3 or later |
Additional Information
- Functionality: The KJ1501X1-BC2 accepts 12 VDC or 24 VDC input and delivers a stable 12 VDC output to power DeltaV system components. Its dual power input design ensures redundancy, minimizing downtime in critical applications. The module supports hot-swappable installation, allowing replacement without interrupting system operation, and includes diagnostics for monitoring power status.
- Environmental Durability: Built for harsh industrial environments, the power supply features conformal coating to protect against airborne contaminants and operates reliably in extreme temperatures, shock, and vibration conditions. It is certified for Zone 2 hazardous area installations, adhering to DeltaV Zone 2 installation guidelines.