Product Description
Model Description
- Model: CE4006P2
- Description: M-series Serial Interface Card, 2-ports (includes 1 Interface Card and a simplex Terminal Block)
- Purpose: Provides a connection between the DeltaV system and devices supporting serial protocols (e.g., Modbus, Allen Bradley's Data Highway Plus)
Hardware Specifications
| Parameter | Specification |
|---|---|
| Number of Serial Ports | 2 |
| Number of Data Sets | 32 (16 per port) |
| Port Types | RS232, RS422/485 half duplex, RS422/485 full duplex |
| Isolation | Each port is isolated from the system and from the other; must be externally grounded |
Communication Specifications
| Parameter | Specification |
|---|---|
| Baud Rate | 300, 1200, 2400, 4800, 9600, 19200, 38400, 57600, 115200 |
| Parity | Even, Odd, None |
| Data Bits | 7 or 8 |
| Stop Bits | 1 or 2 |
| Retry Count | 0-255 |
| Message Time Out | 100-25,500 msec (100 msec increments) |
| Transmit Delay | 0-25,500 msec (100 msec increments) |
| Send Outputs on Startup | Configurable in DeltaV Explorer to enable/disable sending outputs on initialization |
Environmental Specifications
| Parameter | Specification |
|---|---|
| Operating Temperature | -40 to 70°C (-40 to 158°F) |
| Storage Temperature | -40 to 85°C (-40 to 185°F) |
| Relative Humidity | 5 to 95%, non-condensing |
| Airborne Contaminants | ISA-S71.04-1985 Airborne Contaminants Class G3 |
| Hazardous Area/Location | ATEX EEx nA IIC T4; Class 1, Div 2, Groups A, B, C, D, T4 |
| Protection Rating | IP20 |
| Shock | 10 g ½-sine wave for 11 ms |
| Vibration | 3 mm peak-to-peak from 5 to 13 Hz; 0.5 g from 13 to 150 Hz |