Product Description
Model Description
- Model: CE4005S2B1 (comprising KJ3221X1-BA1 AO 4-20 mA HART 8-Channel I/O Card + KJ4001X1-CA1 Standard I/O Termination Block)
- Description: Analog Output Card, 8 Channels, 4-20 mA, HART, compatible with DeltaV M-series Traditional I/O subsystem
- Purpose: Provides analog output signals for process control, supporting HART communication for field devices
-
Features:
- Plug-and-play installation on I/O interface carrier
- Supports simplex and redundant configurations
- Function keying to ensure correct card-to-terminal block compatibility
- Online addition without process interruption
- Meets ISA G3 corrosion specifications with conformal coating
Hardware Specifications
| Parameter | Specification |
|---|---|
| Number of Channels | 8 |
| Isolation | Each channel optically isolated from the system, factory tested to 1500 VDC |
| Nominal Signal Range (Span) | 4 to 20 mA |
| Full Signal Range | 1 to 23 mA |
| Output Compliance | 20 mA at 21.6 VDC supply into 700 Ω load |
| Resolution | 12 bits |
| Accuracy Over Temperature Range | 0.25% of span |
| Calibration | Information stored on card; no manual calibration required |
| Optional Fuse | 2.0 A |
| Terminal Block Keying | A4 (for KJ4001X1-CA1 Standard I/O Termination Block) |
Power Specifications
| Parameter | Specification |
|---|---|
| LocalBus Current (12 VDC Nominal) | 100 mA typical, 150 mA maximum |
| Field Circuit Power per Card | 300 mA maximum at 24 VDC (±10%) |
| Bussed Field Power | 24 VDC at 300 mA |
| Field Circuit | 24 VDC at 23 mA/channel |
Environmental Specifications
| Parameter | Specification |
|---|---|
| Operating Temperature | -40 to 70°C (-40 to 158°F) |
| Storage Temperature | -40 to 85°C (-40 to 185°F) |
| Relative Humidity | 5 to 95%, non-condensing |
| Airborne Contaminants | ISA-S71.04-1985 Airborne Contaminants Class G3; conformal coating |
| Protection Rating | IP20, NEMA 12 |
| Shock | 10 g ½-sine wave for 11 ms |
| Vibration | 1 mm peak-to-peak from 2 to 13.2 Hz; 0.7 g from 13.2 to 150 Hz |
Hazardous Area Certifications
| Parameter | Specification |
|---|---|
| Hazardous Area/Location | ATEX II 3G Ex nA IIC Gc (FM12ATEX0090U); IECEx FMG 12.0035U; Nemko 02ATEX431U (EEx nL IIC); Class I, Div 2, Groups A, B, C, D, T4 |
| Field Wiring | Class I, Div 2, Groups A, B, C, D, T4 non-incendive; ATEX 3 G IIC T4 -nL |
Physical Specifications
| Parameter | Specification |
|---|---|
| Dimensions | Height: 10.7 cm (4.2 in), Width: 4.1 cm (1.6 in), Depth: 10.5 cm (4.1 in) |
Functional Specifications
| Parameter | Specification |
|---|---|
| HART Support | Supports HART pass-through request/response, variable reporting, and field device status reporting |
| Redundancy | Supports 1:1 redundancy with redundant terminal block (CE4035S2B1); autosense by DeltaV; automatic switchover within two scans of I/O bus; make-before-break contacts ensure undisturbed process |
| Switchover Events | Hardware failure, communication failure, field wiring fault, manual initiation via diagnostics explorer |
| I/O Terminal Block Compatibility | Standard I/O Termination Block (KJ4001X1-CA1), Fused I/O Termination Block, 16-Pin Mass I/O Termination Block |
| Pulse Counter | Not applicable for AO card |
| Sequence of Events (SOE) | Not applicable for AO card |
System Compatibility
| Parameter | Specification |
|---|---|
| Compatibility | Compatible with DeltaV M-series controllers; not compatible with S-series controller carriers |
Ordering Information
| Parameter | Specification |
|---|---|
| Model Number | CE4005S2B1 (Analog Output Card: 8 Channels 4-20 mA, HART with Standard I/O Termination Block) |
| Components | KJ3221X1-BA1 (AO 4-20 mA HART 8-Channel I/O Card) + KJ4001X1-CA1 (Standard I/O Termination Block) |
Installation and Maintenance
| Parameter | Specification |
|---|---|
| Installation | Plugs into I/O interface carrier; non-sparking field circuits must be de-energized before removal/insertion; rotary keying system ensures compatibility |
| Removal/Insertion | Cannot be removed/inserted with system power energized in hazardous areas unless confirmed non-hazardous; only one unit at a time |
| Maintenance | No user-serviceable parts; do not disassemble; calibration not required |
| Spare Parts | 250V 2A Fuse for Fused Terminal Block (Model: KJ4010X1-BC1, Box of 20) |