Product Description
Bently Nevada 3300/36-13-12-03-01-00 Temperature Monitor
Product Overview
- The Bently Nevada 3300/36-13-12-03-01-00 Temperature Monitor measures and monitors temperature in rotating machinery, such as turbines, compressors, and motors, across power generation, oil and gas
Technical Specifications
| Specification | Details | 
|---|---|
| Manufacturer | Bently Nevada | 
| Series | 3300 Series | 
| Model/Part Number | 3300/36-13-12-03-01-00 | 
| Model Type | Temperature Monitor | 
| Function | Monitors temperature using thermocouples or RTDs | 
| Processor | Microprocessor-based (specific architecture not publicly detailed) | 
| Memory | Non-volatile memory for configuration and alarm setpoints | 
| Display | Analog meters (two, one per channel) for temperature; LEDs for OK, Alert, Danger, and Bypass | 
| Inputs | 2 temperature sensor inputs (works with thermocouples, like Type J, K, E, T, or 3-wire/4-wire RTDs, such as 100 Ω Pt, 120 Ω Ni) | 
| Outputs | 2 analog outputs (4–20 mA, proportional to temperature) 2 buffered sensor outputs (for external diagnostics) 4 relay outputs (dry contact, up to 5 A at 250 VAC/24 VDC, for Alert and Danger per channel) | 
| Communication Interfaces | Serial interface (RS-232, optional for data logging); connects to 3300 rack backplane for System 1 integration | 
| Signal Conditioning | Linearizes and processes thermocouple/RTD signals; provides cold junction compensation for thermocouples | 
| Temperature Range | Thermocouples: -200°C to +1370°C (-328°F to +2498°F, type-specific) RTDs: -200°C to +850°C (-328°F to +1562°F, type-specific) | 
| Accuracy | ±1% of full-scale range or ±2°C (whichever is greater, with compatible sensor) | 
| Redundancy | Non-redundant | 
| Diagnostics | Detects sensor faults, open/short circuits; provides OK, Alert, and Danger status via LEDs and relays | 
| Compatibility | Works with Bently Nevada 3300 Series rack, thermocouples (Type J, K, E, T), RTDs (100 Ω Pt, 120 Ω Ni), and transducer interface modules; integrates with System 1 software via 3300 rack interface; limited compatibility with 3500 Series via adapters | 
| Power Supply | Receives power via 3300 rack backplane (20–30 VDC, typically 24 VDC) | 
| Power Consumption | Approximately 6–9 W | 
| Environmental Specifications | Operating Temperature: -30°C to +65°C (-22°F to +149°F) Storage Temperature: -40°C to +85°C (-40°F to +185°F) Relative Humidity: 5% to 95% non-condensing Vibration: Complies with IEC 60068-2-6 Shock: Complies with IEC 60068-2-27 | 
| Enclosure | IP20 (installs in 3300 Series rack) | 
| Dimensions | Approximately 152 mm (H) x 76 mm (W) x 305 mm (D) | 
| Weight | Approximately 1.5–2 kg | 
| Mounting | Plugs into 3300 Series rack (slot-specific) | 
| Certifications | Meets CE, CSA, ATEX/IECEx Zone 2 (in approved enclosure), marine certifications, such as DNV, ABS | 
 
           
     
     
     
     
    