Output Channels |
16 digital outputs, individually isolated (8 scheduled, 8 non-scheduled) |
Output Type |
Sinking or sourcing |
Output Voltage Range |
10–30 V DC |
Nominal Output Voltage |
12/24 V DC |
Output Current |
1 A per channel @ 60°C, 2 A per channel @ 30°C, 4 A total per module @ 60°C, 8 A total per module @ 30°C |
On-State Voltage Drop |
1.2 V maximum |
Off-State Leakage Current |
0.5 mA maximum per point |
Signal Delay Time |
1 ms (off to on), 2 ms (on to off) |
Surge Current |
4 A for 10 ms per point, repeatable |
Timing Accuracy |
±16.7 µs for scheduled outputs |
Power Dissipation |
4.8 W maximum |
Backplane Current Load |
350 mA @ 5.1 V DC, 2.5 mA @ 24 V DC |
Isolation |
250 V AC (between outputs and backplane), 1350 V AC (basic insulation test) |
Terminal Connections |
36-pin removable terminal block (RTB) |
Wire Size |
0.2–2.5 mm² (22–14 AWG) |
Minimum Load Current |
1 mA per output |
Operating Temperature |
0°C to 60°C (32°F to 140°F) |
Storage Temperature |
-40°C to 85°C (-40°F to 185°F) |
Humidity |
5% to 95% (non-condensing) |
Vibration Tolerance |
2 G continuous, 30 G shock |
Dimensions |
237.5 mm x 183 mm x 55 mm (9.35 in x 7.20 in x 2.17 in) |
Weight |
0.25 kg (0.55 lb) |
Standards Compliance |
CE, UL, CSA (Class I, Div 2, Groups A, B, C, D), RoHS |
Certifications |
TUV certified for functional safety (SIL 2), requires CIPSync for scheduled outputs |