Input Channels |
6 individually isolated current sourcing inputs |
Input Type |
Current |
Input Current Range |
0–20 mA |
Resolution |
16 bits (0.34 µA/bit) |
Input Impedance |
250 Ω |
Data Format |
Integer (left justified, 2’s complement) or IEEE 32-bit floating point |
Conversion Method |
Sigma-Delta |
Sampling |
Real-time sampling (RTS) |
Update Time |
Configurable, minimum 10 ms per channel |
Common Mode Rejection |
>80 dB at 60 Hz |
Normal Mode Rejection |
>60 dB at 60 Hz |
Accuracy |
±0.4% of full scale at 25°C |
Calibration |
Factory calibrated, user calibration supported |
Power Dissipation |
5.1 W maximum |
Backplane Current Load |
250 mA @ 5.1 V DC, 275 mA @ 24 V DC |
Isolation |
250 V (continuous), reinforced insulation type, inputs to backplane and channel-to-channel |
Terminal Connections |
20-pin removable terminal block (RTB), 1756-TBCH or 1756-TBSH |
Wire Size |
0.2–2.5 mm² (22–14 AWG) |
Operating Temperature |
0°C to 60°C (32°F to 140°F) |
Storage Temperature |
-40°C to 85°C (-40°F to 185°F) |
Humidity |
5% to 95% (non-condensing) |
Vibration Tolerance |
2 G @ 10–500 Hz |
Shock Tolerance |
30 G (operating), 50 G (non-operating) |
Dimensions |
145 mm x 35 mm x 140 mm (5.71 in x 1.38 in x 5.51 in) |
Weight |
0.79 kg (1.74 lb) |
Standards Compliance |
CE, UL, CSA (Class I, Div 2, Groups A, B, C, D), FM, RCM |
Certifications |