| Input Channels | 16 analog inputs (differential, individually isolated) | 
| Input Type | Current (HART compatible) | 
| Input Current Range | 0–20 mA, 4–20 mA | 
| Resolution | 16 bits (0.32 µA/bit for 4–20 mA) | 
| Input Impedance | 250 Ω | 
| Data Format | Integer or floating-point | 
| HART Communication | Supports HART protocol v5, v6, v7 | 
| Conversion Method | Successive approximation | 
| Update Time | 20 ms (single channel), 400 ms (all channels with HART enabled) | 
| Common Mode Rejection | >80 dB at 60 Hz | 
| Normal Mode Rejection | >60 dB at 60 Hz | 
| Accuracy | ±0.4% of full scale at 25°C | 
| Calibration | Factory calibrated, user calibration supported | 
| Power Dissipation | 5.2 W maximum | 
| Backplane Current Load | 200 mA @ 5.1 V DC, 75 mA @ 24 V DC | 
| Isolation | 250 V (continuous), reinforced insulation type, inputs to backplane and channel-to-channel | 
| Terminal Connections | 36-pin removable terminal block (RTB), 1756-TBCH or 1756-TBS6H | 
| Wire Size | 0.2–2.5 mm² (22–14 AWG) | 
| Operating Temperature | 0°C to 60°C (32°F to 140°F) | 
| Storage Temperature | -40°C to 85°C (-40°F to 185°F) | 
| Humidity | 5% to 95% (non-condensing) | 
| Vibration Tolerance | 2 G @ 10–500 Hz | 
| Shock Tolerance | 30 G (operating), 50 G (non-operating) | 
| Dimensions | 145 mm x 35 mm x 140 mm (5.71 in x 1.38 in x 5.51 in) | 
| Weight | 0.4 kg (0.88 lb) | 
| Standards Compliance | CE, UL, CSA (Class I, Div 2, Groups A, B, C, D), FM, RCM | 
| Certifications | TUV certified for functional safety (SIL 2) |