| Protection Functions |
Differential protection (87T), overcurrent (50/51), restricted earth fault (87N), thermal overload (49) |
| Measurement Capabilities |
Current, voltage, and temperature monitoring; supports 3-phase current inputs |
| Binary Inputs/Outputs |
12 binary inputs, 8 output contacts (configurable) |
| Communication Interfaces |
1x Ethernet port (IEC 61850, DNP3, Modbus TCP), 1x serial port (SPA, IEC 60870-5-103) |
| Power Supply |
24-265 V AC/DC |
| Operating Temperature Range |
-25°C to +55°C |
| Mounting |
DIN rail or panel mount in control cabinet |
| Dimensions |
177 mm x 100 mm x 50 mm (W x H x D) approximate |
| Weight |
0.6 kg |
| Protection Rating |
IP20 |
| Standards Compliance |
IEC 60255, IEC 61850, CE, UL, CSA |