| Input Channels |
32 digital inputs (single-ended, optically isolated) |
| Input Type |
120 V AC / 230 V AC, 47_63 Hz |
| Rated Voltage |
79_132 V AC / 159_264 V AC (auto-range) |
| Logic 1 (min) |
79 V AC |
| Logic 0 (max) |
20 V AC |
| Input Current |
6 mA typical @ 120 V, 8 mA @ 230 V |
| Input Delay |
Configurable: 3, 5, 10, 20 ms (default 10 ms) |
| Zero-Cross Detection |
Yes _ synchronized to AC mains for noise immunity |
| Cable Length |
200 m (shielded), 100 m (unshielded) |
| Isolation |
1500 V AC input-to-backplane; group isolation (16 channels per group) |
| Common Mode Voltage |
±250 V AC max |
| Diagnostics |
Module fault, missing AC voltage, fuse blown (per group), process alarm, per-group LED
|
| Address Space |
4 bytes (32 inputs) |
| Power Supply |
From S7-300 backplane (5 V DC) |
| Backplane Current |
150 mA @ 5 V DC |
| Power Loss |
8.0 W typical |
| LED Indicators |
- 0_31 (green, grouped): Input state - SF (red): System fault - FUSE (red): Fuse blown per group |
| Configuration |
STEP 7 V5.6+ or TIA Portal V13+; per-group filter, diagnostics, alarm enable |
| Connection |
Front 40-pin connector (6ES7392-1AM00-0AA0, screw or spring) |
| Wire Size |
0.2_1.5 mm² (24_16 AWG) |
| Operating Temperature Range |
0°C to +60°C |
| Storage Temperature Range |
-40°C to +70°C |
| Humidity |
5% to 95% non-condensing |
| Vibration |
IEC 60068-2-6 (1g, 10_150 Hz) |
| Shock |
IEC 60068-2-27 (15g, 11 ms) |
| Mounting |
Snaps onto S7-300 rail
|
| Dimensions (W x H x D) |
40 mm _ 125 mm _ 120 mm |
| Weight |
0.28 kg |
| Enclosure Rating |
IP20 |
| Certifications |
CE, UL, cUL, FM Class I Div 2, ATEX Zone 2, China RoHS, EAC
|