| Specification |
Details |
| Model |
IS200TBAIH1CDD |
| Series |
Mark VI Speedtronic |
| Type |
Analog Input Terminal Board (TBAI) |
| Function |
Interfaces with analog input signals for turbine monitoring |
| Input/Output Capabilities |
10 analog inputs (1–5 V DC, supports 2/3/4-wire or externally powered transmitters), 2 analog outputs (4–20 mA or 0–200 mA) |
| Compatible Module |
VAIC Analog Input Board (IS200VAICH1) |
| Power Supply |
+24 V DC (current-limited, supplied by VAIC for transducers) |
| Output Load |
500 Ω for 4–20 mA, 50 Ω for 0–200 mA |
| Connectors |
Two terminal strips (TB1, TB2 with 48 screw-type terminals), multi-pin connectors for VAIC module |
| Signal Protection |
Noise suppression for surges and high-frequency interference, shield terminals for grounding |
| Synchronization |
±1 ns accuracy in TMR setups |
| Components |
Surface-mount technology, terminal blocks, resistors, capacitors, integrated circuits |
| Power Consumption |
Less than 31 W |
| Board Size |
Approx. 15.9 cm high x 17.8 cm wide (6.26 x 7.01 in) |
| Coating |
Conformal coating for environmental protection |
| Board Markings |
GE logo, IS200TBAIH1CDD, 6BA01 code |
| Operating Temperature |
0°C to +60°C (32°F to +140°F) |
| Storage Temperature |
-40°C to +85°C (-40°F to +185°F) |
| Relative Humidity |
5% to 95% (non-condensing) |
| Weight |
Approx. 0.5 kg (1.1 lbs) |
| Mounting |
Single slot in Mark VI rack, flat or DIN-rail mount |
| Certifications |
CE, UL, CSA, Class I Div 2 |
| Compatibility |
Mark VI Turbine Control System, Proficy Machine Edition |
| Manual |
GEH-6421 |