| Input Channels |
4 differential RTD inputs (2-wire or 3-wire) |
| RTD Types Supported |
Pt100, Pt1000, Ni100, Ni120, Ni1000, Cu10, Cu50, Cu100 (α = 0.00385, 0.00392, 0.00427) |
| Temperature Range |
-200°C to +850°C (depends on RTD type) |
| Resolution |
0.1°C (16-bit) |
| Accuracy |
±0.5°C typical (±1.0°C max) after calibration |
| Excitation Current |
1 mA constant current source per channel |
| Lead Resistance Compensation |
Automatic for 3-wire; manual offset for 2-wire |
| Update Rate |
100 ms for all 4 channels |
| Input Impedance |
>10 MΩ |
| Open Wire Detection |
Yes _ detects broken or disconnected leads |
| Isolation |
1500 V RMS field-to-backplane; 250 V RMS channel-to-channel |
| Common Mode Rejection |
>100 dB @ 50/60 Hz |
| Filtering |
Digital low-pass filter (configurable 0.1_10 Hz); 50/60 Hz notch |
| Linearization |
Automatic per IEC 60751 / DIN 43760 standards |
| Scaling |
Configurable engineering units (°C, °F, K) via PME |
| Diagnostics |
Open circuit, overrange, underrange, module fault, excitation fault |
| Power Supply |
+5 V DC @ 120 mA (from backplane) |
| Power Consumption |
0.6 W maximum |
| LED Indicators |
Module OK (green), Fault (red), 4x Channel Active (green) |
| Configuration |
Via Proficy Machine Edition (PME); per-channel RTD type, filtering, alarms |
| Operating Temperature Range |
0°C to +60°C |
| Storage Temperature Range |
-40°C to +85°C |
| Humidity |
5% to 95% non-condensing |
| Vibration |
IEC 60068-2-6 (5g, 10_150 Hz) |
| Shock |
IEC 60068-2-27 (30g, 11 ms) |
| Mounting |
Snaps onto VersaMax carrier base (IC200ACCxxx) |
| Dimensions |
4.33" x 2.60" x 1.77" (110 mm x 66 mm x 45 mm) |
| Weight |
0.44 lb (0.20 kg) |
| Enclosure Rating |
IP20 |
| Standards Compliance |
IEC 61131-2, CE, UL, CSA, Class I Division 2, ATEX Zone 2, RoHS compliant |